🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

5 Amp Wire Size at 75 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 5 A load over a 75 ft (22.9 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 1.93%
Aluminum Wire (≤3% Drop)3 AWGDrop: 0.3V (2.52%)
Voltage at Load End11.8 VLoss: 0.23 V (1.2 W)
Power & Breaker (125%)0.06 kW10A Breaker Recommended

All AWG & kcmil Wire Gauges for 5 Amps at 75 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2.35 V (19.6%)9.6 V3.88 V (32.33%)11.8 WDrop/Amp High
12 AWG3.31 mm²20 A1.48 V (12.32%)10.5 V2.44 V (20.32%)7.4 WDrop/Amp High
10 AWG5.26 mm²30 A0.93 V (7.75%)11.1 V1.53 V (12.78%)4.7 WDrop/Amp High
8 AWG8.37 mm²50 A0.58 V (4.87%)11.4 V0.96 V (8.03%)2.9 W~ ≤5%
6 AWG13.3 mm²65 A0.37 V (3.07%)11.6 V0.61 V (5.06%)1.8 W~ ≤5%
4 AWG21.15 mm²85 A0.23 V (1.93%)11.8 V0.38 V (3.18%)1.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.18 V (1.53%)11.8 V0.3 V (2.52%)0.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.15 V (1.21%)11.9 V0.24 V (2.0%)0.7 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.12 V (0.96%)11.9 V0.19 V (1.59%)0.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.09 V (0.76%)11.9 V0.15 V (1.26%)0.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.07 V (0.6%)11.9 V0.12 V (1.0%)0.4 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.06 V (0.48%)11.9 V0.09 V (0.79%)0.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.05 V (0.38%)12.0 V0.08 V (0.63%)0.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.04 V (0.32%)12.0 V0.06 V (0.53%)0.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.03 V (0.27%)12.0 V0.05 V (0.44%)0.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.03 V (0.23%)12.0 V0.05 V (0.38%)0.1 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.02 V (0.2%)12.0 V0.04 V (0.33%)0.1 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.02 V (0.16%)12.0 V0.03 V (0.27%)0.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.02 V (0.13%)12.0 V0.03 V (0.22%)0.1 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.01 V (0.11%)12.0 V0.02 V (0.18%)0.1 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.01 V (0.08%)12.0 V0.02 V (0.13%)0.0 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 5 amps at 75 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 5A load over 75 feet one-way at 12V (DC), you need 4 AWG copper wire. This produces a voltage drop of 0.23V (1.93%) and delivers 11.8V at the load.

What size aluminum wire is required for 5 amps at 75 feet?

Using aluminum conductors (75°C rating), you should use 3 AWG to maintain voltage drop at 0.3V (2.52%).

What breaker size is needed for a 5A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (5A × 1.25 = 6.2A), which corresponds to a standard 10A circuit breaker.