🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

5 Amp Wire Size at 225 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 5 A load over a 225 ft (68.6 m) one-way run.

Copper Wire (≤3% Drop)14 AWG2.08 mm² · Drop: 1.27%
Aluminum Wire (≤3% Drop)14 AWGDrop: 10.08V (2.1%)
Voltage at Load End473.9 VLoss: 6.11 V (52.9 W)
Power & Breaker (125%)4.16 kW10A Breaker Recommended

All AWG & kcmil Wire Gauges for 5 Amps at 225 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A6.11 V (1.27%)473.9 V10.08 V (2.1%)52.9 W✓ PASS (≤3%)
12 AWG3.31 mm²20 A3.84 V (0.8%)476.2 V6.33 V (1.32%)33.3 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A2.42 V (0.5%)477.6 V3.99 V (0.83%)20.9 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A1.52 V (0.32%)478.5 V2.5 V (0.52%)13.2 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A0.96 V (0.2%)479.0 V1.58 V (0.33%)8.3 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.6 V (0.13%)479.4 V0.99 V (0.21%)5.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.48 V (0.1%)479.5 V0.79 V (0.16%)4.1 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.38 V (0.08%)479.6 V0.62 V (0.13%)3.3 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.3 V (0.06%)479.7 V0.49 V (0.1%)2.6 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.24 V (0.05%)479.8 V0.39 V (0.08%)2.1 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.19 V (0.04%)479.8 V0.31 V (0.06%)1.6 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.15 V (0.03%)479.9 V0.25 V (0.05%)1.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.12 V (0.02%)479.9 V0.2 V (0.04%)1.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.1 V (0.02%)479.9 V0.17 V (0.03%)0.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.08 V (0.02%)479.9 V0.14 V (0.03%)0.7 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.07 V (0.01%)479.9 V0.12 V (0.02%)0.6 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.06 V (0.01%)479.9 V0.1 V (0.02%)0.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.05 V (0.01%)479.9 V0.08 V (0.02%)0.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.04 V (0.01%)480.0 V0.07 V (0.01%)0.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.03 V (0.01%)480.0 V0.06 V (0.01%)0.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.01%)480.0 V0.04 V (0.01%)0.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 5 amps at 225 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 5A load over 225 feet one-way at 480V (3-Phase), you need 14 AWG copper wire. This produces a voltage drop of 6.11V (1.27%) and delivers 473.9V at the load.

What size aluminum wire is required for 5 amps at 225 feet?

Using aluminum conductors (75°C rating), you should use 14 AWG to maintain voltage drop at 10.08V (2.1%).

What breaker size is needed for a 5A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (5A × 1.25 = 6.2A), which corresponds to a standard 10A circuit breaker.