⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

5 Amp Wire Size at 250 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 5 A load over a 250 ft (76.2 m) one-way run.

Copper Wire (≤3% Drop)14 AWG2.08 mm² · Drop: 1.41%
Aluminum Wire (≤3% Drop)14 AWGDrop: 11.2V (2.33%)
Voltage at Load End473.2 VLoss: 6.79 V (58.8 W)
Power & Breaker (125%)4.16 kW10A Breaker Recommended

All AWG & kcmil Wire Gauges for 5 Amps at 250 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A6.79 V (1.41%)473.2 V11.2 V (2.33%)58.8 W✓ PASS (≤3%)
12 AWG3.31 mm²20 A4.27 V (0.89%)475.7 V7.04 V (1.47%)36.9 W✓ PASS (≤3%)
10 AWG5.26 mm²30 A2.68 V (0.56%)477.3 V4.43 V (0.92%)23.3 W✓ PASS (≤3%)
8 AWG8.37 mm²50 A1.69 V (0.35%)478.3 V2.78 V (0.58%)14.6 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.06 V (0.22%)478.9 V1.75 V (0.36%)9.2 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A0.67 V (0.14%)479.3 V1.1 V (0.23%)5.8 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.53 V (0.11%)479.5 V0.87 V (0.18%)4.6 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.42 V (0.09%)479.6 V0.69 V (0.14%)3.6 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.33 V (0.07%)479.7 V0.55 V (0.11%)2.9 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.26 V (0.06%)479.7 V0.44 V (0.09%)2.3 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.21 V (0.04%)479.8 V0.35 V (0.07%)1.8 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.17 V (0.03%)479.8 V0.27 V (0.06%)1.4 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.13 V (0.03%)479.9 V0.22 V (0.05%)1.1 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.11 V (0.02%)479.9 V0.18 V (0.04%)1.0 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.09 V (0.02%)479.9 V0.15 V (0.03%)0.8 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.08 V (0.02%)479.9 V0.13 V (0.03%)0.7 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.07 V (0.01%)479.9 V0.11 V (0.02%)0.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.06 V (0.01%)479.9 V0.09 V (0.02%)0.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.05 V (0.01%)480.0 V0.08 V (0.02%)0.4 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.04 V (0.01%)480.0 V0.06 V (0.01%)0.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.03 V (0.01%)480.0 V0.05 V (0.01%)0.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 5 amps at 250 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 5A load over 250 feet one-way at 480V (3-Phase), you need 14 AWG copper wire. This produces a voltage drop of 6.79V (1.41%) and delivers 473.2V at the load.

What size aluminum wire is required for 5 amps at 250 feet?

Using aluminum conductors (75°C rating), you should use 14 AWG to maintain voltage drop at 11.2V (2.33%).

What breaker size is needed for a 5A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (5A × 1.25 = 6.2A), which corresponds to a standard 10A circuit breaker.