⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

50 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 50 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)3 AWG26.67 mm² · Drop: 2.8%
Aluminum Wire (≤3% Drop)1 AWGDrop: 6.04V (2.9%)
Voltage at Load End202.2 VLoss: 5.82 V (504.4 W)
Power & Breaker (125%)18.01 kW63A Breaker Recommended

All AWG & kcmil Wire Gauges for 50 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A74.68 V (35.91%)133.3 V123.19 V (59.23%)6467.8 WDrop/Amp High
12 AWG3.31 mm²20 A46.93 V (22.56%)161.1 V77.41 V (37.22%)4064.4 WDrop/Amp High
10 AWG5.26 mm²30 A29.53 V (14.2%)178.5 V48.72 V (23.42%)2557.6 WDrop/Amp High
8 AWG8.37 mm²50 A18.56 V (8.92%)189.4 V30.61 V (14.72%)1607.3 WDrop/Amp High
6 AWG13.3 mm²65 A11.68 V (5.62%)196.3 V19.27 V (9.26%)1011.5 WDrop/Amp High
4 AWG21.15 mm²85 A7.34 V (3.53%)200.7 V12.12 V (5.82%)636.1 W~ ≤5%
3 AWG26.67 mm²100 A5.82 V (2.8%)202.2 V9.61 V (4.62%)504.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A4.62 V (2.22%)203.4 V7.62 V (3.66%)400.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A3.66 V (1.76%)204.3 V6.04 V (2.9%)317.2 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A2.9 V (1.4%)205.1 V4.79 V (2.3%)251.5 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A2.3 V (1.11%)205.7 V3.8 V (1.83%)199.5 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A1.83 V (0.88%)206.2 V3.01 V (1.45%)158.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A1.45 V (0.7%)206.6 V2.39 V (1.15%)125.5 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A1.23 V (0.59%)206.8 V2.02 V (0.97%)106.2 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A1.02 V (0.49%)207.0 V1.69 V (0.81%)88.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.88 V (0.42%)207.1 V1.45 V (0.69%)75.9 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.77 V (0.37%)207.2 V1.26 V (0.61%)66.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.61 V (0.29%)207.4 V1.01 V (0.49%)53.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.51 V (0.25%)207.5 V0.84 V (0.41%)44.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.41 V (0.2%)207.6 V0.67 V (0.32%)35.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.31 V (0.15%)207.7 V0.51 V (0.24%)26.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 50 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 50A load over 275 feet one-way at 208V (3-Phase), you need 3 AWG copper wire. This produces a voltage drop of 5.82V (2.8%) and delivers 202.2V at the load.

What size aluminum wire is required for 50 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1 AWG to maintain voltage drop at 6.04V (2.9%).

What breaker size is needed for a 50A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (50A × 1.25 = 62.5A), which corresponds to a standard 63A circuit breaker.