🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

15 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 15 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)6 AWGDrop: 5.78V (2.78%)
Voltage at Load End202.4 VLoss: 5.57 V (144.7 W)
Power & Breaker (125%)5.4 kW20A Breaker Recommended

All AWG & kcmil Wire Gauges for 15 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A22.41 V (10.77%)185.6 V36.96 V (17.77%)582.1 WDrop/Amp High
12 AWG3.31 mm²20 A14.08 V (6.77%)193.9 V23.22 V (11.17%)365.8 WDrop/Amp High
10 AWG5.26 mm²30 A8.86 V (4.26%)199.1 V14.61 V (7.03%)230.2 W~ ≤5%
8 AWG8.37 mm²50 A5.57 V (2.68%)202.4 V9.18 V (4.42%)144.7 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A3.5 V (1.68%)204.5 V5.78 V (2.78%)91.0 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A2.2 V (1.06%)205.8 V3.63 V (1.75%)57.2 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.75 V (0.84%)206.3 V2.88 V (1.39%)45.4 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.39 V (0.67%)206.6 V2.29 V (1.1%)36.0 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.1 V (0.53%)206.9 V1.81 V (0.87%)28.5 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.87 V (0.42%)207.1 V1.44 V (0.69%)22.6 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.69 V (0.33%)207.3 V1.14 V (0.55%)18.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.55 V (0.26%)207.5 V0.9 V (0.43%)14.2 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.43 V (0.21%)207.6 V0.72 V (0.34%)11.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.37 V (0.18%)207.6 V0.61 V (0.29%)9.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.31 V (0.15%)207.7 V0.51 V (0.24%)8.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.26 V (0.13%)207.7 V0.43 V (0.21%)6.8 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.23 V (0.11%)207.8 V0.38 V (0.18%)6.0 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.18 V (0.09%)207.8 V0.3 V (0.15%)4.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.15 V (0.07%)207.8 V0.25 V (0.12%)4.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.12 V (0.06%)207.9 V0.2 V (0.1%)3.2 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.09 V (0.04%)207.9 V0.15 V (0.07%)2.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 15 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 15A load over 275 feet one-way at 208V (3-Phase), you need 8 AWG copper wire. This produces a voltage drop of 5.57V (2.68%) and delivers 202.4V at the load.

What size aluminum wire is required for 15 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 5.78V (2.78%).

What breaker size is needed for a 15A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (15A × 1.25 = 18.8A), which corresponds to a standard 20A circuit breaker.