🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

100 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 100 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)1/0 AWG53.49 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)3/0 AWGDrop: 6.03V (2.9%)
Voltage at Load End202.2 VLoss: 5.81 V (1006.0 W)
Power & Breaker (125%)36.03 kW125A Breaker Recommended

All AWG & kcmil Wire Gauges for 100 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A149.37 V (71.81%)58.6 V246.39 V (118.46%)25871.4 WDrop/Amp High
12 AWG3.31 mm²20 A93.86 V (45.13%)114.1 V154.83 V (74.44%)16257.5 WDrop/Amp High
10 AWG5.26 mm²30 A59.07 V (28.4%)148.9 V97.43 V (46.84%)10230.5 WDrop/Amp High
8 AWG8.37 mm²50 A37.12 V (17.85%)170.9 V61.23 V (29.44%)6429.2 WDrop/Amp High
6 AWG13.3 mm²65 A23.36 V (11.23%)184.6 V38.53 V (18.53%)4046.0 WDrop/Amp High
4 AWG21.15 mm²85 A14.69 V (7.06%)193.3 V24.23 V (11.65%)2544.3 WDrop/Amp High
3 AWG26.67 mm²100 A11.65 V (5.6%)196.4 V19.22 V (9.24%)2017.7 WDrop/Amp High
2 AWG33.62 mm²115 A9.24 V (4.44%)198.8 V15.24 V (7.33%)1600.6 W~ ≤5%
1 AWG42.41 mm²130 A7.33 V (3.52%)200.7 V12.08 V (5.81%)1268.9 W~ ≤5%
1/0 AWG53.49 mm²150 A5.81 V (2.79%)202.2 V9.58 V (4.61%)1006.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A4.61 V (2.22%)203.4 V7.6 V (3.65%)798.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A3.65 V (1.76%)204.3 V6.03 V (2.9%)633.0 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A2.9 V (1.39%)205.1 V4.78 V (2.3%)502.0 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A2.45 V (1.18%)205.5 V4.04 V (1.94%)424.7 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.04 V (0.98%)206.0 V3.37 V (1.62%)354.0 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A1.75 V (0.84%)206.2 V2.89 V (1.39%)303.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.53 V (0.74%)206.5 V2.53 V (1.22%)265.5 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.23 V (0.59%)206.8 V2.02 V (0.97%)212.4 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.02 V (0.49%)207.0 V1.69 V (0.81%)177.0 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.82 V (0.39%)207.2 V1.35 V (0.65%)141.6 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.61 V (0.29%)207.4 V1.01 V (0.49%)106.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 100 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 100A load over 275 feet one-way at 208V (3-Phase), you need 1/0 AWG copper wire. This produces a voltage drop of 5.81V (2.79%) and delivers 202.2V at the load.

What size aluminum wire is required for 100 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 3/0 AWG to maintain voltage drop at 6.03V (2.9%).

What breaker size is needed for a 100A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (100A × 1.25 = 125.0A), which corresponds to a standard 125A circuit breaker.