⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

125 Amp Wire Size at 275 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 125 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.77%
Aluminum Wire (≤3% Drop)4/0 AWGDrop: 5.98V (2.87%)
Voltage at Load End202.2 VLoss: 5.76 V (1247.0 W)
Power & Breaker (125%)45.03 kW160A Breaker Recommended

All AWG & kcmil Wire Gauges for 125 Amps at 275 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A186.71 V (89.76%)21.3 V307.99 V (148.07%)40424.0 WDrop/Amp High
12 AWG3.31 mm²20 A117.33 V (56.41%)90.7 V193.54 V (93.05%)25402.4 WDrop/Amp High
10 AWG5.26 mm²30 A73.83 V (35.5%)134.2 V121.79 V (58.55%)15985.2 WDrop/Amp High
8 AWG8.37 mm²50 A46.4 V (22.31%)161.6 V76.54 V (36.8%)10045.6 WDrop/Amp High
6 AWG13.3 mm²65 A29.2 V (14.04%)178.8 V48.17 V (23.16%)6322.0 WDrop/Amp High
4 AWG21.15 mm²85 A18.36 V (8.83%)189.6 V30.29 V (14.56%)3975.5 WDrop/Amp High
3 AWG26.67 mm²100 A14.56 V (7.0%)193.4 V24.02 V (11.55%)3152.7 WDrop/Amp High
2 AWG33.62 mm²115 A11.55 V (5.55%)196.4 V19.05 V (9.16%)2500.9 WDrop/Amp High
1 AWG42.41 mm²130 A9.16 V (4.4%)198.8 V15.11 V (7.26%)1982.6 W~ ≤5%
1/0 AWG53.49 mm²150 A7.26 V (3.49%)200.7 V11.98 V (5.76%)1571.9 W~ ≤5%
2/0 AWG67.43 mm²175 A5.76 V (2.77%)202.2 V9.5 V (4.57%)1247.0 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A4.57 V (2.2%)203.4 V7.54 V (3.62%)989.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A3.62 V (1.74%)204.4 V5.98 V (2.87%)784.3 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.07 V (1.47%)204.9 V5.06 V (2.43%)663.6 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A2.55 V (1.23%)205.4 V4.21 V (2.03%)553.2 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.19 V (1.05%)205.8 V3.61 V (1.74%)474.2 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A1.92 V (0.92%)206.1 V3.16 V (1.52%)414.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.53 V (0.74%)206.5 V2.53 V (1.22%)331.8 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.28 V (0.61%)206.7 V2.11 V (1.01%)276.6 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.02 V (0.49%)207.0 V1.69 V (0.81%)221.3 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.77 V (0.37%)207.2 V1.26 V (0.61%)165.9 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 125 amps at 275 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 125A load over 275 feet one-way at 208V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 5.76V (2.77%) and delivers 202.2V at the load.

What size aluminum wire is required for 125 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 4/0 AWG to maintain voltage drop at 5.98V (2.87%).

What breaker size is needed for a 125A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (125A × 1.25 = 156.2A), which corresponds to a standard 160A circuit breaker.