⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

50 Amp Wire Size at 40 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 50 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)8 AWG8.37 mm² · Drop: 1.3%
Aluminum Wire (≤3% Drop)6 AWGDrop: 3.24V (1.35%)
Voltage at Load End236.9 VLoss: 3.12 V (155.9 W)
Power & Breaker (125%)12.0 kW63A Breaker Recommended

All AWG & kcmil Wire Gauges for 50 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A12.54 V (5.23%)227.5 V20.69 V (8.62%)627.2 WDrop/Amp High
12 AWG3.31 mm²20 A7.88 V (3.28%)232.1 V13.0 V (5.42%)394.1 WDrop/Amp High
10 AWG5.26 mm²30 A4.96 V (2.07%)235.0 V8.18 V (3.41%)248.0 WDrop/Amp High
8 AWG8.37 mm²50 A3.12 V (1.3%)236.9 V5.14 V (2.14%)155.9 W✓ PASS (≤3%)
6 AWG13.3 mm²65 A1.96 V (0.82%)238.0 V3.24 V (1.35%)98.1 W✓ PASS (≤3%)
4 AWG21.15 mm²85 A1.23 V (0.51%)238.8 V2.03 V (0.85%)61.7 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A0.98 V (0.41%)239.0 V1.61 V (0.67%)48.9 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A0.78 V (0.32%)239.2 V1.28 V (0.53%)38.8 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A0.62 V (0.26%)239.4 V1.01 V (0.42%)30.8 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.49 V (0.2%)239.5 V0.8 V (0.34%)24.4 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.39 V (0.16%)239.6 V0.64 V (0.27%)19.3 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.31 V (0.13%)239.7 V0.51 V (0.21%)15.3 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.24 V (0.1%)239.8 V0.4 V (0.17%)12.2 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.21 V (0.09%)239.8 V0.34 V (0.14%)10.3 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.17 V (0.07%)239.8 V0.28 V (0.12%)8.6 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.15 V (0.06%)239.9 V0.24 V (0.1%)7.4 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.13 V (0.05%)239.9 V0.21 V (0.09%)6.4 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.1 V (0.04%)239.9 V0.17 V (0.07%)5.1 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.09 V (0.04%)239.9 V0.14 V (0.06%)4.3 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.07 V (0.03%)239.9 V0.11 V (0.05%)3.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.05 V (0.02%)239.9 V0.08 V (0.04%)2.6 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 50 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 50A load over 40 feet one-way at 240V (1-Phase), you need 8 AWG copper wire. This produces a voltage drop of 3.12V (1.3%) and delivers 236.9V at the load.

What size aluminum wire is required for 50 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 6 AWG to maintain voltage drop at 3.24V (1.35%).

What breaker size is needed for a 50A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (50A × 1.25 = 62.5A), which corresponds to a standard 63A circuit breaker.