🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 1000 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.68%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 18.39V (8.84%)
Voltage at Load End202.4 VLoss: 5.58 V (4827.4 W)
Power & Breaker (125%)180.13 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 1000 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A2715.79 V (1305.67%)0.0 V4479.78 V (2153.74%)2351942.3 WDrop/Amp High
12 AWG3.31 mm²20 A1706.6 V (820.48%)0.0 V2815.09 V (1353.41%)1477957.7 WDrop/Amp High
10 AWG5.26 mm²30 A1073.92 V (516.31%)0.0 V1771.47 V (851.67%)930045.6 WDrop/Amp High
8 AWG8.37 mm²50 A674.89 V (324.47%)0.0 V1113.26 V (535.22%)584473.1 WDrop/Amp High
6 AWG13.3 mm²65 A424.72 V (204.19%)0.0 V700.6 V (336.83%)367822.6 WDrop/Amp High
4 AWG21.15 mm²85 A267.08 V (128.41%)0.0 V440.56 V (211.81%)231302.1 WDrop/Amp High
3 AWG26.67 mm²100 A211.81 V (101.83%)0.0 V349.38 V (167.97%)183428.6 WDrop/Amp High
2 AWG33.62 mm²115 A168.02 V (80.78%)40.0 V277.15 V (133.25%)145509.8 WDrop/Amp High
1 AWG42.41 mm²130 A133.2 V (64.04%)74.8 V219.71 V (105.63%)115351.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A105.61 V (50.77%)102.4 V174.2 V (83.75%)91457.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A83.77 V (40.28%)124.2 V138.19 V (66.44%)72549.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A66.45 V (31.95%)141.6 V109.61 V (52.7%)57546.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A52.69 V (25.33%)155.3 V86.92 V (41.79%)45634.7 WDrop/Amp High
250 kcmil126.7 mm²255 A44.58 V (21.43%)163.4 V73.54 V (35.36%)38611.2 WDrop/Amp High
300 kcmil152.0 mm²285 A37.16 V (17.87%)170.8 V61.3 V (29.47%)32184.5 WDrop/Amp High
350 kcmil177.3 mm²310 A31.86 V (15.32%)176.1 V52.55 V (25.27%)27591.9 WDrop/Amp High
400 kcmil202.7 mm²335 A27.87 V (13.4%)180.1 V45.97 V (22.1%)24134.4 WDrop/Amp High
500 kcmil253.4 mm²380 A22.29 V (10.72%)185.7 V36.77 V (17.68%)19305.6 WDrop/Amp High
600 kcmil304.0 mm²420 A18.58 V (8.93%)189.4 V30.65 V (14.74%)16092.2 WDrop/Amp High
750 kcmil380.0 mm²475 A14.87 V (7.15%)193.1 V24.52 V (11.79%)12873.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A11.15 V (5.36%)196.9 V18.39 V (8.84%)9654.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 1000 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 1000 feet one-way at 208V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.58V (2.68%) and delivers 202.4V at the load.

What size aluminum wire is required for 500 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 18.39V (8.84%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.