🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 500 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)1000 kcmil506.7 mm² · Drop: 1.16%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.19V (1.92%)
Voltage at Load End474.4 VLoss: 5.57 V (4827.4 W)
Power & Breaker (125%)415.69 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 500 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1357.89 V (282.89%)0.0 V2239.89 V (466.64%)1175971.2 WDrop/Amp High
12 AWG3.31 mm²20 A853.3 V (177.77%)0.0 V1407.55 V (293.24%)738978.9 WDrop/Amp High
10 AWG5.26 mm²30 A536.96 V (111.87%)0.0 V885.74 V (184.53%)465022.8 WDrop/Amp High
8 AWG8.37 mm²50 A337.45 V (70.3%)142.6 V556.63 V (115.96%)292236.6 WDrop/Amp High
6 AWG13.3 mm²65 A212.36 V (44.24%)267.6 V350.3 V (72.98%)183911.3 WDrop/Amp High
4 AWG21.15 mm²85 A133.54 V (27.82%)346.5 V220.28 V (45.89%)115651.1 WDrop/Amp High
3 AWG26.67 mm²100 A105.9 V (22.06%)374.1 V174.69 V (36.39%)91714.3 WDrop/Amp High
2 AWG33.62 mm²115 A84.01 V (17.5%)396.0 V138.58 V (28.87%)72754.9 WDrop/Amp High
1 AWG42.41 mm²130 A66.6 V (13.87%)413.4 V109.86 V (22.89%)57675.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A52.8 V (11.0%)427.2 V87.1 V (18.15%)45728.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A41.89 V (8.73%)438.1 V69.09 V (14.39%)36275.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A33.22 V (6.92%)446.8 V54.81 V (11.42%)28773.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A26.35 V (5.49%)453.7 V43.46 V (9.05%)22817.4 WDrop/Amp High
250 kcmil126.7 mm²255 A22.29 V (4.64%)457.7 V36.77 V (7.66%)19305.6 WDrop/Amp High
300 kcmil152.0 mm²285 A18.58 V (3.87%)461.4 V30.65 V (6.39%)16092.2 WDrop/Amp High
350 kcmil177.3 mm²310 A15.93 V (3.32%)464.1 V26.28 V (5.47%)13795.9 WDrop/Amp High
400 kcmil202.7 mm²335 A13.93 V (2.9%)466.1 V22.98 V (4.79%)12067.2 WDrop/Amp High
500 kcmil253.4 mm²380 A11.15 V (2.32%)468.9 V18.39 V (3.83%)9652.8 WDrop/Amp High
600 kcmil304.0 mm²420 A9.29 V (1.94%)470.7 V15.33 V (3.19%)8046.1 WDrop/Amp High
750 kcmil380.0 mm²475 A7.43 V (1.55%)472.6 V12.26 V (2.55%)6436.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.57 V (1.16%)474.4 V9.19 V (1.92%)4827.4 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 500 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 500 feet one-way at 480V (3-Phase), you need 1000 kcmil copper wire. This produces a voltage drop of 5.57V (1.16%) and delivers 474.4V at the load.

What size aluminum wire is required for 500 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.19V (1.92%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.