⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

500 Amp Wire Size at 600 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 500 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.61%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 12.74V (5.31%)
Voltage at Load End236.1 VLoss: 3.86 V (1931.0 W)
Power & Breaker (125%)120.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 500 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1881.55 V (783.98%)0.0 V3103.68 V (1293.2%)940776.9 WDrop/Amp High
12 AWG3.31 mm²20 A1182.37 V (492.65%)0.0 V1950.35 V (812.65%)591183.1 WDrop/Amp High
10 AWG5.26 mm²30 A744.04 V (310.02%)0.0 V1227.31 V (511.38%)372018.3 WDrop/Amp High
8 AWG8.37 mm²50 A467.58 V (194.82%)0.0 V771.29 V (321.37%)233789.2 WDrop/Amp High
6 AWG13.3 mm²65 A294.26 V (122.61%)0.0 V485.39 V (202.25%)147129.0 WDrop/Amp High
4 AWG21.15 mm²85 A185.04 V (77.1%)55.0 V305.23 V (127.18%)92520.9 WDrop/Amp High
3 AWG26.67 mm²100 A146.74 V (61.14%)93.3 V242.06 V (100.86%)73371.4 WDrop/Amp High
2 AWG33.62 mm²115 A116.41 V (48.5%)123.6 V192.02 V (80.01%)58203.9 WDrop/Amp High
1 AWG42.41 mm²130 A92.28 V (38.45%)147.7 V152.22 V (63.43%)46140.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A73.17 V (30.49%)166.8 V120.69 V (50.29%)36582.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A58.04 V (24.18%)182.0 V95.74 V (39.89%)29020.0 WDrop/Amp High
3/0 AWG85.01 mm²200 A46.04 V (19.18%)194.0 V75.94 V (31.64%)23018.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A36.51 V (15.21%)203.5 V60.22 V (25.09%)18253.9 WDrop/Amp High
250 kcmil126.7 mm²255 A30.89 V (12.87%)209.1 V50.95 V (21.23%)15444.5 WDrop/Amp High
300 kcmil152.0 mm²285 A25.75 V (10.73%)214.3 V42.47 V (17.7%)12873.8 WDrop/Amp High
350 kcmil177.3 mm²310 A22.07 V (9.2%)217.9 V36.41 V (15.17%)11036.8 WDrop/Amp High
400 kcmil202.7 mm²335 A19.31 V (8.04%)220.7 V31.85 V (13.27%)9653.8 WDrop/Amp High
500 kcmil253.4 mm²380 A15.44 V (6.44%)224.6 V25.48 V (10.62%)7722.2 WDrop/Amp High
600 kcmil304.0 mm²420 A12.87 V (5.36%)227.1 V21.24 V (8.85%)6436.9 WDrop/Amp High
750 kcmil380.0 mm²475 A10.3 V (4.29%)229.7 V16.99 V (7.08%)5149.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A7.72 V (3.22%)232.3 V12.74 V (5.31%)3861.9 W~ ≤5%

Frequently Asked Engineering Questions

What size copper wire do I need for 500 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 500A load over 600 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.86V (1.61%) and delivers 236.1V at the load.

What size aluminum wire is required for 500 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 12.74V (5.31%).

What breaker size is needed for a 500A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (500A × 1.25 = 625.0A), which corresponds to a standard 700A circuit breaker.