🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 100 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.26%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.02V (0.84%)
Voltage at Load End239.4 VLoss: 0.61 V (584.1 W)
Power & Breaker (125%)228.63 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 100 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A298.74 V (124.47%)0.0 V492.78 V (205.32%)284585.0 WDrop/Amp High
12 AWG3.31 mm²20 A187.73 V (78.22%)52.3 V309.66 V (129.02%)178832.9 WDrop/Amp High
10 AWG5.26 mm²30 A118.13 V (49.22%)121.9 V194.86 V (81.19%)112535.5 WDrop/Amp High
8 AWG8.37 mm²50 A74.24 V (30.93%)165.8 V122.46 V (51.02%)70721.2 WDrop/Amp High
6 AWG13.3 mm²65 A46.72 V (19.47%)193.3 V77.07 V (32.11%)44506.5 WDrop/Amp High
4 AWG21.15 mm²85 A29.38 V (12.24%)210.6 V48.46 V (20.19%)27987.6 WDrop/Amp High
3 AWG26.67 mm²100 A23.3 V (9.71%)216.7 V38.43 V (16.01%)22194.9 WDrop/Amp High
2 AWG33.62 mm²115 A18.48 V (7.7%)221.5 V30.49 V (12.7%)17606.7 WDrop/Amp High
1 AWG42.41 mm²130 A14.65 V (6.1%)225.3 V24.17 V (10.07%)13957.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.62 V (4.84%)228.4 V19.16 V (7.98%)11066.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.22 V (3.84%)230.8 V15.2 V (6.33%)8778.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.31 V (3.05%)232.7 V12.06 V (5.02%)6963.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.8 V (2.42%)234.2 V9.56 V (3.98%)5521.8 WDrop/Amp High
250 kcmil126.7 mm²255 A4.9 V (2.04%)235.1 V8.09 V (3.37%)4672.0 WDrop/Amp High
300 kcmil152.0 mm²285 A4.09 V (1.7%)235.9 V6.74 V (2.81%)3894.3 WDrop/Amp High
350 kcmil177.3 mm²310 A3.5 V (1.46%)236.5 V5.78 V (2.41%)3338.6 WDrop/Amp High
400 kcmil202.7 mm²335 A3.07 V (1.28%)236.9 V5.06 V (2.11%)2920.3 WDrop/Amp High
500 kcmil253.4 mm²380 A2.45 V (1.02%)237.5 V4.04 V (1.69%)2336.0 WDrop/Amp High
600 kcmil304.0 mm²420 A2.04 V (0.85%)238.0 V3.37 V (1.4%)1947.2 WDrop/Amp High
750 kcmil380.0 mm²475 A1.64 V (0.68%)238.4 V2.7 V (1.12%)1557.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.23 V (0.51%)238.8 V2.02 V (0.84%)1168.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 100 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 100 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.61V (0.26%) and delivers 239.4V at the load.

What size aluminum wire is required for 550 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.02V (0.84%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.