⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 120 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.3%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.43V (1.01%)
Voltage at Load End239.3 VLoss: 0.73 V (701.0 W)
Power & Breaker (125%)228.63 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A358.48 V (149.37%)0.0 V591.33 V (246.39%)341502.0 WDrop/Amp High
12 AWG3.31 mm²20 A225.27 V (93.86%)14.7 V371.59 V (154.83%)214599.5 WDrop/Amp High
10 AWG5.26 mm²30 A141.76 V (59.07%)98.2 V233.83 V (97.43%)135042.6 WDrop/Amp High
8 AWG8.37 mm²50 A89.09 V (37.12%)150.9 V146.95 V (61.23%)84865.5 WDrop/Amp High
6 AWG13.3 mm²65 A56.06 V (23.36%)183.9 V92.48 V (38.53%)53407.8 WDrop/Amp High
4 AWG21.15 mm²85 A35.26 V (14.69%)204.7 V58.15 V (24.23%)33585.1 WDrop/Amp High
3 AWG26.67 mm²100 A27.96 V (11.65%)212.0 V46.12 V (19.22%)26633.8 WDrop/Amp High
2 AWG33.62 mm²115 A22.18 V (9.24%)217.8 V36.58 V (15.24%)21128.0 WDrop/Amp High
1 AWG42.41 mm²130 A17.58 V (7.33%)222.4 V29.0 V (12.08%)16749.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.94 V (5.81%)226.1 V22.99 V (9.58%)13279.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.06 V (4.61%)228.9 V18.24 V (7.6%)10534.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.77 V (3.65%)231.2 V14.47 V (6.03%)8355.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.96 V (2.9%)233.0 V11.47 V (4.78%)6626.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.89 V (2.45%)234.1 V9.71 V (4.04%)5606.3 WDrop/Amp High
300 kcmil152.0 mm²285 A4.91 V (2.04%)235.1 V8.09 V (3.37%)4673.2 WDrop/Amp High
350 kcmil177.3 mm²310 A4.21 V (1.75%)235.8 V6.94 V (2.89%)4006.3 WDrop/Amp High
400 kcmil202.7 mm²335 A3.68 V (1.53%)236.3 V6.07 V (2.53%)3504.3 WDrop/Amp High
500 kcmil253.4 mm²380 A2.94 V (1.23%)237.1 V4.85 V (2.02%)2803.2 WDrop/Amp High
600 kcmil304.0 mm²420 A2.45 V (1.02%)237.5 V4.05 V (1.69%)2336.6 WDrop/Amp High
750 kcmil380.0 mm²475 A1.96 V (0.82%)238.0 V3.24 V (1.35%)1869.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.47 V (0.61%)238.5 V2.43 V (1.01%)1401.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 120 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.73V (0.3%) and delivers 239.3V at the load.

What size aluminum wire is required for 550 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.43V (1.01%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.