🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 50 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.13%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.01V (0.42%)
Voltage at Load End239.7 VLoss: 0.3 V (292.1 W)
Power & Breaker (125%)228.63 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 50 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A149.37 V (62.24%)90.6 V246.39 V (102.66%)142292.5 WDrop/Amp High
12 AWG3.31 mm²20 A93.86 V (39.11%)146.1 V154.83 V (64.51%)89416.4 WDrop/Amp High
10 AWG5.26 mm²30 A59.07 V (24.61%)180.9 V97.43 V (40.6%)56267.8 WDrop/Amp High
8 AWG8.37 mm²50 A37.12 V (15.47%)202.9 V61.23 V (25.51%)35360.6 WDrop/Amp High
6 AWG13.3 mm²65 A23.36 V (9.73%)216.6 V38.53 V (16.06%)22253.3 WDrop/Amp High
4 AWG21.15 mm²85 A14.69 V (6.12%)225.3 V24.23 V (10.1%)13993.8 WDrop/Amp High
3 AWG26.67 mm²100 A11.65 V (4.85%)228.4 V19.22 V (8.01%)11097.4 WDrop/Amp High
2 AWG33.62 mm²115 A9.24 V (3.85%)230.8 V15.24 V (6.35%)8803.3 WDrop/Amp High
1 AWG42.41 mm²130 A7.33 V (3.05%)232.7 V12.08 V (5.04%)6978.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.81 V (2.42%)234.2 V9.58 V (3.99%)5533.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.61 V (1.92%)235.4 V7.6 V (3.17%)4389.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.65 V (1.52%)236.3 V6.03 V (2.51%)3481.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.9 V (1.21%)237.1 V4.78 V (1.99%)2760.9 WDrop/Amp High
250 kcmil126.7 mm²255 A2.45 V (1.02%)237.5 V4.04 V (1.69%)2336.0 WDrop/Amp High
300 kcmil152.0 mm²285 A2.04 V (0.85%)238.0 V3.37 V (1.4%)1947.2 WDrop/Amp High
350 kcmil177.3 mm²310 A1.75 V (0.73%)238.2 V2.89 V (1.2%)1669.3 WDrop/Amp High
400 kcmil202.7 mm²335 A1.53 V (0.64%)238.5 V2.53 V (1.05%)1460.1 WDrop/Amp High
500 kcmil253.4 mm²380 A1.23 V (0.51%)238.8 V2.02 V (0.84%)1168.0 WDrop/Amp High
600 kcmil304.0 mm²420 A1.02 V (0.43%)239.0 V1.69 V (0.7%)973.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.82 V (0.34%)239.2 V1.35 V (0.56%)778.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.61 V (0.26%)239.4 V1.01 V (0.42%)584.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 50 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 50 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.3V (0.13%) and delivers 239.7V at the load.

What size aluminum wire is required for 550 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.01V (0.42%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.