🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 60 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 60 ft (18.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.15%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.21V (0.51%)
Voltage at Load End239.6 VLoss: 0.37 V (350.4 W)
Power & Breaker (125%)228.63 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 60 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A179.24 V (74.68%)60.8 V295.67 V (123.19%)170751.0 WDrop/Amp High
12 AWG3.31 mm²20 A112.64 V (46.93%)127.4 V185.8 V (77.41%)107299.7 WDrop/Amp High
10 AWG5.26 mm²30 A70.88 V (29.53%)169.1 V116.92 V (48.72%)67521.3 WDrop/Amp High
8 AWG8.37 mm²50 A44.54 V (18.56%)195.5 V73.47 V (30.61%)42432.7 WDrop/Amp High
6 AWG13.3 mm²65 A28.03 V (11.68%)212.0 V46.24 V (19.27%)26703.9 WDrop/Amp High
4 AWG21.15 mm²85 A17.63 V (7.34%)222.4 V29.08 V (12.12%)16792.5 WDrop/Amp High
3 AWG26.67 mm²100 A13.98 V (5.82%)226.0 V23.06 V (9.61%)13316.9 WDrop/Amp High
2 AWG33.62 mm²115 A11.09 V (4.62%)228.9 V18.29 V (7.62%)10564.0 WDrop/Amp High
1 AWG42.41 mm²130 A8.79 V (3.66%)231.2 V14.5 V (6.04%)8374.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.97 V (2.9%)233.0 V11.5 V (4.79%)6639.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.53 V (2.3%)234.5 V9.12 V (3.8%)5267.1 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.39 V (1.83%)235.6 V7.23 V (3.01%)4177.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.48 V (1.45%)236.5 V5.74 V (2.39%)3313.1 WDrop/Amp High
250 kcmil126.7 mm²255 A2.94 V (1.23%)237.1 V4.85 V (2.02%)2803.2 WDrop/Amp High
300 kcmil152.0 mm²285 A2.45 V (1.02%)237.5 V4.05 V (1.69%)2336.6 WDrop/Amp High
350 kcmil177.3 mm²310 A2.1 V (0.88%)237.9 V3.47 V (1.45%)2003.2 WDrop/Amp High
400 kcmil202.7 mm²335 A1.84 V (0.77%)238.2 V3.03 V (1.26%)1752.2 WDrop/Amp High
500 kcmil253.4 mm²380 A1.47 V (0.61%)238.5 V2.43 V (1.01%)1401.6 WDrop/Amp High
600 kcmil304.0 mm²420 A1.23 V (0.51%)238.8 V2.02 V (0.84%)1168.3 WDrop/Amp High
750 kcmil380.0 mm²475 A0.98 V (0.41%)239.0 V1.62 V (0.67%)934.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.74 V (0.31%)239.3 V1.21 V (0.51%)700.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 60 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 60 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.37V (0.15%) and delivers 239.6V at the load.

What size aluminum wire is required for 550 amps at 60 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.21V (0.51%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.