⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 80 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.2%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.62V (0.67%)
Voltage at Load End239.5 VLoss: 0.49 V (467.3 W)
Power & Breaker (125%)228.63 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A238.99 V (99.58%)1.0 V394.22 V (164.26%)227668.0 WDrop/Amp High
12 AWG3.31 mm²20 A150.18 V (62.58%)89.8 V247.73 V (103.22%)143066.3 WDrop/Amp High
10 AWG5.26 mm²30 A94.51 V (39.38%)145.5 V155.89 V (64.95%)90028.4 WDrop/Amp High
8 AWG8.37 mm²50 A59.39 V (24.75%)180.6 V97.97 V (40.82%)56577.0 WDrop/Amp High
6 AWG13.3 mm²65 A37.38 V (15.57%)202.6 V61.65 V (25.69%)35605.2 WDrop/Amp High
4 AWG21.15 mm²85 A23.5 V (9.79%)216.5 V38.77 V (16.15%)22390.0 WDrop/Amp High
3 AWG26.67 mm²100 A18.64 V (7.77%)221.4 V30.75 V (12.81%)17755.9 WDrop/Amp High
2 AWG33.62 mm²115 A14.79 V (6.16%)225.2 V24.39 V (10.16%)14085.4 WDrop/Amp High
1 AWG42.41 mm²130 A11.72 V (4.88%)228.3 V19.33 V (8.06%)11166.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A9.29 V (3.87%)230.7 V15.33 V (6.39%)8853.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A7.37 V (3.07%)232.6 V12.16 V (5.07%)7022.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A5.85 V (2.44%)234.2 V9.65 V (4.02%)5570.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A4.64 V (1.93%)235.4 V7.65 V (3.19%)4417.4 WDrop/Amp High
250 kcmil126.7 mm²255 A3.92 V (1.63%)236.1 V6.47 V (2.7%)3737.6 WDrop/Amp High
300 kcmil152.0 mm²285 A3.27 V (1.36%)236.7 V5.39 V (2.25%)3115.5 WDrop/Amp High
350 kcmil177.3 mm²310 A2.8 V (1.17%)237.2 V4.62 V (1.93%)2670.9 WDrop/Amp High
400 kcmil202.7 mm²335 A2.45 V (1.02%)237.5 V4.05 V (1.69%)2336.2 WDrop/Amp High
500 kcmil253.4 mm²380 A1.96 V (0.82%)238.0 V3.24 V (1.35%)1868.8 WDrop/Amp High
600 kcmil304.0 mm²420 A1.64 V (0.68%)238.4 V2.7 V (1.12%)1557.7 WDrop/Amp High
750 kcmil380.0 mm²475 A1.31 V (0.55%)238.7 V2.16 V (0.9%)1246.2 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.98 V (0.41%)239.0 V1.62 V (0.67%)934.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 80 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.49V (0.2%) and delivers 239.5V at the load.

What size aluminum wire is required for 550 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.62V (0.67%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.