🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 1000 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 23.36V (19.46%)
Voltage at Load End116.5 VLoss: 3.54 V (1947.0 W)
Power & Breaker (125%)66.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 1000 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3449.52 V (2874.6%)0.0 V5690.09 V (4741.74%)1897233.5 WDrop/Amp High
12 AWG3.31 mm²20 A2167.67 V (1806.39%)0.0 V3575.64 V (2979.7%)1192219.2 WDrop/Amp High
10 AWG5.26 mm²30 A1364.07 V (1136.72%)0.0 V2250.07 V (1875.06%)750236.8 WDrop/Amp High
8 AWG8.37 mm²50 A857.23 V (714.36%)0.0 V1414.02 V (1178.35%)471475.0 WDrop/Amp High
6 AWG13.3 mm²65 A539.47 V (449.56%)0.0 V889.88 V (741.57%)296710.2 WDrop/Amp High
4 AWG21.15 mm²85 A339.24 V (282.7%)0.0 V559.59 V (466.33%)186583.7 WDrop/Amp High
3 AWG26.67 mm²100 A269.03 V (224.19%)0.0 V443.77 V (369.81%)147965.7 WDrop/Amp High
2 AWG33.62 mm²115 A213.41 V (177.85%)0.0 V352.03 V (293.36%)117377.9 WDrop/Amp High
1 AWG42.41 mm²130 A169.18 V (140.98%)0.0 V279.07 V (232.56%)93049.9 WDrop/Amp High
1/0 AWG53.49 mm²150 A134.14 V (111.78%)0.0 V221.26 V (184.39%)73775.4 WDrop/Amp High
2/0 AWG67.43 mm²175 A106.41 V (88.67%)13.6 V175.52 V (146.27%)58523.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A84.4 V (70.33%)35.6 V139.22 V (116.02%)46421.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A66.93 V (55.78%)53.1 V110.4 V (92.0%)36812.0 WDrop/Amp High
250 kcmil126.7 mm²255 A56.63 V (47.19%)63.4 V93.41 V (77.84%)31146.4 WDrop/Amp High
300 kcmil152.0 mm²285 A47.2 V (39.34%)72.8 V77.86 V (64.89%)25962.1 WDrop/Amp High
350 kcmil177.3 mm²310 A40.47 V (33.72%)79.5 V66.75 V (55.63%)22257.4 WDrop/Amp High
400 kcmil202.7 mm²335 A35.4 V (29.5%)84.6 V58.39 V (48.66%)19468.4 WDrop/Amp High
500 kcmil253.4 mm²380 A28.31 V (23.6%)91.7 V46.71 V (38.92%)15573.2 WDrop/Amp High
600 kcmil304.0 mm²420 A23.6 V (19.67%)96.4 V38.93 V (32.44%)12981.1 WDrop/Amp High
750 kcmil380.0 mm²475 A18.88 V (15.73%)101.1 V31.15 V (25.95%)10384.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A14.16 V (11.8%)105.8 V23.36 V (19.46%)7788.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 1000 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 1000 feet one-way at 120V (1-Phase), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.54V (2.95%) and delivers 116.5V at the load.

What size aluminum wire is required for 550 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 23.36V (19.46%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.