⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 20 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.03%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.4V (0.08%)
Voltage at Load End479.9 VLoss: 0.12 V (116.8 W)
Power & Breaker (125%)457.26 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 20 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A59.75 V (12.45%)420.3 V98.56 V (20.53%)56917.0 WDrop/Amp High
12 AWG3.31 mm²20 A37.55 V (7.82%)442.5 V61.93 V (12.9%)35766.6 WDrop/Amp High
10 AWG5.26 mm²30 A23.63 V (4.92%)456.4 V38.97 V (8.12%)22507.1 WDrop/Amp High
8 AWG8.37 mm²50 A14.85 V (3.09%)465.2 V24.49 V (5.1%)14144.2 WDrop/Amp High
6 AWG13.3 mm²65 A9.34 V (1.95%)470.7 V15.41 V (3.21%)8901.3 WDrop/Amp High
4 AWG21.15 mm²85 A5.88 V (1.22%)474.1 V9.69 V (2.02%)5597.5 WDrop/Amp High
3 AWG26.67 mm²100 A4.66 V (0.97%)475.3 V7.69 V (1.6%)4439.0 WDrop/Amp High
2 AWG33.62 mm²115 A3.7 V (0.77%)476.3 V6.1 V (1.27%)3521.3 WDrop/Amp High
1 AWG42.41 mm²130 A2.93 V (0.61%)477.1 V4.83 V (1.01%)2791.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A2.32 V (0.48%)477.7 V3.83 V (0.8%)2213.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A1.84 V (0.38%)478.2 V3.04 V (0.63%)1755.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.46 V (0.3%)478.5 V2.41 V (0.5%)1392.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.16 V (0.24%)478.8 V1.91 V (0.4%)1104.4 WDrop/Amp High
250 kcmil126.7 mm²255 A0.98 V (0.2%)479.0 V1.62 V (0.34%)934.4 WDrop/Amp High
300 kcmil152.0 mm²285 A0.82 V (0.17%)479.2 V1.35 V (0.28%)778.9 WDrop/Amp High
350 kcmil177.3 mm²310 A0.7 V (0.15%)479.3 V1.16 V (0.24%)667.7 WDrop/Amp High
400 kcmil202.7 mm²335 A0.61 V (0.13%)479.4 V1.01 V (0.21%)584.1 WDrop/Amp High
500 kcmil253.4 mm²380 A0.49 V (0.1%)479.5 V0.81 V (0.17%)467.2 WDrop/Amp High
600 kcmil304.0 mm²420 A0.41 V (0.09%)479.6 V0.67 V (0.14%)389.4 WDrop/Amp High
750 kcmil380.0 mm²475 A0.33 V (0.07%)479.7 V0.54 V (0.11%)311.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.25 V (0.05%)479.8 V0.4 V (0.08%)233.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 20 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 20 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.12V (0.03%) and delivers 479.9V at the load.

What size aluminum wire is required for 550 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.4V (0.08%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.