⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 100 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.13%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.02V (0.42%)
Voltage at Load End479.4 VLoss: 0.61 V (584.1 W)
Power & Breaker (125%)457.26 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 100 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A298.74 V (62.24%)181.3 V492.78 V (102.66%)284585.0 WDrop/Amp High
12 AWG3.31 mm²20 A187.73 V (39.11%)292.3 V309.66 V (64.51%)178832.9 WDrop/Amp High
10 AWG5.26 mm²30 A118.13 V (24.61%)361.9 V194.86 V (40.6%)112535.5 WDrop/Amp High
8 AWG8.37 mm²50 A74.24 V (15.47%)405.8 V122.46 V (25.51%)70721.2 WDrop/Amp High
6 AWG13.3 mm²65 A46.72 V (9.73%)433.3 V77.07 V (16.06%)44506.5 WDrop/Amp High
4 AWG21.15 mm²85 A29.38 V (6.12%)450.6 V48.46 V (10.1%)27987.6 WDrop/Amp High
3 AWG26.67 mm²100 A23.3 V (4.85%)456.7 V38.43 V (8.01%)22194.9 WDrop/Amp High
2 AWG33.62 mm²115 A18.48 V (3.85%)461.5 V30.49 V (6.35%)17606.7 WDrop/Amp High
1 AWG42.41 mm²130 A14.65 V (3.05%)465.3 V24.17 V (5.04%)13957.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.62 V (2.42%)468.4 V19.16 V (3.99%)11066.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.22 V (1.92%)470.8 V15.2 V (3.17%)8778.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.31 V (1.52%)472.7 V12.06 V (2.51%)6963.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.8 V (1.21%)474.2 V9.56 V (1.99%)5521.8 WDrop/Amp High
250 kcmil126.7 mm²255 A4.9 V (1.02%)475.1 V8.09 V (1.69%)4672.0 WDrop/Amp High
300 kcmil152.0 mm²285 A4.09 V (0.85%)475.9 V6.74 V (1.4%)3894.3 WDrop/Amp High
350 kcmil177.3 mm²310 A3.5 V (0.73%)476.5 V5.78 V (1.2%)3338.6 WDrop/Amp High
400 kcmil202.7 mm²335 A3.07 V (0.64%)476.9 V5.06 V (1.05%)2920.3 WDrop/Amp High
500 kcmil253.4 mm²380 A2.45 V (0.51%)477.5 V4.04 V (0.84%)2336.0 WDrop/Amp High
600 kcmil304.0 mm²420 A2.04 V (0.43%)478.0 V3.37 V (0.7%)1947.2 WDrop/Amp High
750 kcmil380.0 mm²475 A1.64 V (0.34%)478.4 V2.7 V (0.56%)1557.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.23 V (0.26%)478.8 V2.02 V (0.42%)1168.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 100 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 100 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.61V (0.13%) and delivers 479.4V at the load.

What size aluminum wire is required for 550 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.02V (0.42%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.