🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 120 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.15%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.43V (0.51%)
Voltage at Load End479.3 VLoss: 0.73 V (701.0 W)
Power & Breaker (125%)457.26 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 120 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A358.48 V (74.68%)121.5 V591.33 V (123.19%)341502.0 WDrop/Amp High
12 AWG3.31 mm²20 A225.27 V (46.93%)254.7 V371.59 V (77.41%)214599.5 WDrop/Amp High
10 AWG5.26 mm²30 A141.76 V (29.53%)338.2 V233.83 V (48.72%)135042.6 WDrop/Amp High
8 AWG8.37 mm²50 A89.09 V (18.56%)390.9 V146.95 V (30.61%)84865.5 WDrop/Amp High
6 AWG13.3 mm²65 A56.06 V (11.68%)423.9 V92.48 V (19.27%)53407.8 WDrop/Amp High
4 AWG21.15 mm²85 A35.26 V (7.34%)444.7 V58.15 V (12.12%)33585.1 WDrop/Amp High
3 AWG26.67 mm²100 A27.96 V (5.82%)452.0 V46.12 V (9.61%)26633.8 WDrop/Amp High
2 AWG33.62 mm²115 A22.18 V (4.62%)457.8 V36.58 V (7.62%)21128.0 WDrop/Amp High
1 AWG42.41 mm²130 A17.58 V (3.66%)462.4 V29.0 V (6.04%)16749.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A13.94 V (2.9%)466.1 V22.99 V (4.79%)13279.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.06 V (2.3%)468.9 V18.24 V (3.8%)10534.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A8.77 V (1.83%)471.2 V14.47 V (3.01%)8355.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.96 V (1.45%)473.0 V11.47 V (2.39%)6626.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.89 V (1.23%)474.1 V9.71 V (2.02%)5606.3 WDrop/Amp High
300 kcmil152.0 mm²285 A4.91 V (1.02%)475.1 V8.09 V (1.69%)4673.2 WDrop/Amp High
350 kcmil177.3 mm²310 A4.21 V (0.88%)475.8 V6.94 V (1.45%)4006.3 WDrop/Amp High
400 kcmil202.7 mm²335 A3.68 V (0.77%)476.3 V6.07 V (1.26%)3504.3 WDrop/Amp High
500 kcmil253.4 mm²380 A2.94 V (0.61%)477.1 V4.85 V (1.01%)2803.2 WDrop/Amp High
600 kcmil304.0 mm²420 A2.45 V (0.51%)477.5 V4.05 V (0.84%)2336.6 WDrop/Amp High
750 kcmil380.0 mm²475 A1.96 V (0.41%)478.0 V3.24 V (0.67%)1869.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.47 V (0.31%)478.5 V2.43 V (0.51%)1401.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 120 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 120 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.73V (0.15%) and delivers 479.3V at the load.

What size aluminum wire is required for 550 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.43V (0.51%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.