🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 30 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.04%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.61V (0.13%)
Voltage at Load End479.8 VLoss: 0.18 V (175.2 W)
Power & Breaker (125%)457.26 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 30 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A89.62 V (18.67%)390.4 V147.83 V (30.8%)85375.5 WDrop/Amp High
12 AWG3.31 mm²20 A56.32 V (11.73%)423.7 V92.9 V (19.35%)53649.9 WDrop/Amp High
10 AWG5.26 mm²30 A35.44 V (7.38%)444.6 V58.46 V (12.18%)33760.7 WDrop/Amp High
8 AWG8.37 mm²50 A22.27 V (4.64%)457.7 V36.74 V (7.65%)21216.4 WDrop/Amp High
6 AWG13.3 mm²65 A14.02 V (2.92%)466.0 V23.12 V (4.82%)13352.0 WDrop/Amp High
4 AWG21.15 mm²85 A8.81 V (1.84%)471.2 V14.54 V (3.03%)8396.3 WDrop/Amp High
3 AWG26.67 mm²100 A6.99 V (1.46%)473.0 V11.53 V (2.4%)6658.5 WDrop/Amp High
2 AWG33.62 mm²115 A5.54 V (1.16%)474.5 V9.15 V (1.91%)5282.0 WDrop/Amp High
1 AWG42.41 mm²130 A4.4 V (0.92%)475.6 V7.25 V (1.51%)4187.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.48 V (0.73%)476.5 V5.75 V (1.2%)3319.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.76 V (0.58%)477.2 V4.56 V (0.95%)2633.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.19 V (0.46%)477.8 V3.62 V (0.75%)2088.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.74 V (0.36%)478.3 V2.87 V (0.6%)1656.5 WDrop/Amp High
250 kcmil126.7 mm²255 A1.47 V (0.31%)478.5 V2.43 V (0.51%)1401.6 WDrop/Amp High
300 kcmil152.0 mm²285 A1.23 V (0.26%)478.8 V2.02 V (0.42%)1168.3 WDrop/Amp High
350 kcmil177.3 mm²310 A1.05 V (0.22%)478.9 V1.73 V (0.36%)1001.6 WDrop/Amp High
400 kcmil202.7 mm²335 A0.92 V (0.19%)479.1 V1.52 V (0.32%)876.1 WDrop/Amp High
500 kcmil253.4 mm²380 A0.74 V (0.15%)479.3 V1.21 V (0.25%)700.8 WDrop/Amp High
600 kcmil304.0 mm²420 A0.61 V (0.13%)479.4 V1.01 V (0.21%)584.1 WDrop/Amp High
750 kcmil380.0 mm²475 A0.49 V (0.1%)479.5 V0.81 V (0.17%)467.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.37 V (0.08%)479.6 V0.61 V (0.13%)350.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 30 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 30 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.18V (0.04%) and delivers 479.8V at the load.

What size aluminum wire is required for 550 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.61V (0.13%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.