⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 400 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.36%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.34V (7.79%)
Voltage at Load End117.2 VLoss: 2.83 V (1557.7 W)
Power & Breaker (125%)66.0 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 400 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1379.81 V (1149.84%)0.0 V2276.04 V (1896.7%)758893.4 WDrop/Amp High
12 AWG3.31 mm²20 A867.07 V (722.56%)0.0 V1430.26 V (1191.88%)476887.7 WDrop/Amp High
10 AWG5.26 mm²30 A545.63 V (454.69%)0.0 V900.03 V (750.02%)300094.7 WDrop/Amp High
8 AWG8.37 mm²50 A342.89 V (285.74%)0.0 V565.61 V (471.34%)188590.0 WDrop/Amp High
6 AWG13.3 mm²65 A215.79 V (179.82%)0.0 V355.95 V (296.63%)118684.1 WDrop/Amp High
4 AWG21.15 mm²85 A135.7 V (113.08%)0.0 V223.84 V (186.53%)74633.5 WDrop/Amp High
3 AWG26.67 mm²100 A107.61 V (89.68%)12.4 V177.51 V (147.92%)59186.3 WDrop/Amp High
2 AWG33.62 mm²115 A85.37 V (71.14%)34.6 V140.81 V (117.34%)46951.2 WDrop/Amp High
1 AWG42.41 mm²130 A67.67 V (56.39%)52.3 V111.63 V (93.02%)37220.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A53.65 V (44.71%)66.3 V88.51 V (73.75%)29510.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A42.56 V (35.47%)77.4 V70.21 V (58.51%)23409.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A33.76 V (28.13%)86.2 V55.69 V (46.41%)18568.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A26.77 V (22.31%)93.2 V44.16 V (36.8%)14724.8 WDrop/Amp High
250 kcmil126.7 mm²255 A22.65 V (18.88%)97.3 V37.37 V (31.14%)12458.5 WDrop/Amp High
300 kcmil152.0 mm²285 A18.88 V (15.73%)101.1 V31.15 V (25.95%)10384.9 WDrop/Amp High
350 kcmil177.3 mm²310 A16.19 V (13.49%)103.8 V26.7 V (22.25%)8903.0 WDrop/Amp High
400 kcmil202.7 mm²335 A14.16 V (11.8%)105.8 V23.36 V (19.46%)7787.4 WDrop/Amp High
500 kcmil253.4 mm²380 A11.33 V (9.44%)108.7 V18.68 V (15.57%)6229.3 WDrop/Amp High
600 kcmil304.0 mm²420 A9.44 V (7.87%)110.6 V15.57 V (12.98%)5192.4 WDrop/Amp High
750 kcmil380.0 mm²475 A7.55 V (6.29%)112.4 V12.46 V (10.38%)4153.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.66 V (4.72%)114.3 V9.34 V (7.79%)3115.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 400 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 400 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.83V (2.36%) and delivers 117.2V at the load.

What size aluminum wire is required for 550 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.34V (7.79%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.