🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

550 Amp Wire Size at 400 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 550 A load over a 400 ft (121.9 m) one-way run.

Copper Wire (≤3% Drop)16× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 9.34V (77.86%)
Voltage at Load End11.7 VLoss: 0.35 V (194.7 W)
Power & Breaker (125%)6.6 kW700A Breaker Recommended

All AWG & kcmil Wire Gauges for 550 Amps at 400 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1379.81 V (11498.38%)0.0 V2276.04 V (18966.96%)758893.4 WDrop/Amp High
12 AWG3.31 mm²20 A867.07 V (7225.57%)0.0 V1430.26 V (11918.82%)476887.7 WDrop/Amp High
10 AWG5.26 mm²30 A545.63 V (4546.89%)0.0 V900.03 V (7500.24%)300094.7 WDrop/Amp High
8 AWG8.37 mm²50 A342.89 V (2857.42%)0.0 V565.61 V (4713.41%)188590.0 WDrop/Amp High
6 AWG13.3 mm²65 A215.79 V (1798.24%)0.0 V355.95 V (2966.26%)118684.1 WDrop/Amp High
4 AWG21.15 mm²85 A135.7 V (1130.81%)0.0 V223.84 V (1865.31%)74633.5 WDrop/Amp High
3 AWG26.67 mm²100 A107.61 V (896.76%)0.0 V177.51 V (1479.24%)59186.3 WDrop/Amp High
2 AWG33.62 mm²115 A85.37 V (711.38%)0.0 V140.81 V (1173.45%)46951.2 WDrop/Amp High
1 AWG42.41 mm²130 A67.67 V (563.94%)0.0 V111.63 V (930.24%)37220.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A53.65 V (447.12%)0.0 V88.51 V (737.54%)29510.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A42.56 V (354.69%)0.0 V70.21 V (585.07%)23409.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A33.76 V (281.34%)0.0 V55.69 V (464.08%)18568.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A26.77 V (223.1%)0.0 V44.16 V (368.02%)14724.8 WDrop/Amp High
250 kcmil126.7 mm²255 A22.65 V (188.77%)0.0 V37.37 V (311.38%)12458.5 WDrop/Amp High
300 kcmil152.0 mm²285 A18.88 V (157.35%)0.0 V31.15 V (259.55%)10384.9 WDrop/Amp High
350 kcmil177.3 mm²310 A16.19 V (134.89%)0.0 V26.7 V (222.51%)8903.0 WDrop/Amp High
400 kcmil202.7 mm²335 A14.16 V (117.99%)0.0 V23.36 V (194.63%)7787.4 WDrop/Amp High
500 kcmil253.4 mm²380 A11.33 V (94.38%)0.7 V18.68 V (155.69%)6229.3 WDrop/Amp High
600 kcmil304.0 mm²420 A9.44 V (78.67%)2.6 V15.57 V (129.77%)5192.4 WDrop/Amp High
750 kcmil380.0 mm²475 A7.55 V (62.94%)4.4 V12.46 V (103.82%)4153.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.66 V (47.2%)6.3 V9.34 V (77.86%)3115.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 550 amps at 400 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 550A load over 400 feet one-way at 12V (DC), you need 16× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.95%) and delivers 11.7V at the load.

What size aluminum wire is required for 550 amps at 400 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 9.34V (77.86%).

What breaker size is needed for a 550A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (550A × 1.25 = 687.5A), which corresponds to a standard 700A circuit breaker.