⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

80 Amp Wire Size at 50 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 80 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)4 AWG21.15 mm² · Drop: 1.03%
Aluminum Wire (≤3% Drop)2 AWGDrop: 2.56V (1.07%)
Voltage at Load End237.5 VLoss: 2.47 V (197.4 W)
Power & Breaker (125%)19.2 kW100A Breaker Recommended

All AWG & kcmil Wire Gauges for 80 Amps at 50 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A25.09 V (10.45%)214.9 V41.38 V (17.24%)2007.0 WDrop/Amp High
12 AWG3.31 mm²20 A15.76 V (6.57%)224.2 V26.0 V (10.84%)1261.2 WDrop/Amp High
10 AWG5.26 mm²30 A9.92 V (4.13%)230.1 V16.36 V (6.82%)793.6 WDrop/Amp High
8 AWG8.37 mm²50 A6.23 V (2.6%)233.8 V10.28 V (4.28%)498.8 WDrop/Amp High
6 AWG13.3 mm²65 A3.92 V (1.63%)236.1 V6.47 V (2.7%)313.9 WDrop/Amp High
4 AWG21.15 mm²85 A2.47 V (1.03%)237.5 V4.07 V (1.7%)197.4 W✓ PASS (≤3%)
3 AWG26.67 mm²100 A1.96 V (0.82%)238.0 V3.23 V (1.34%)156.5 W✓ PASS (≤3%)
2 AWG33.62 mm²115 A1.55 V (0.65%)238.4 V2.56 V (1.07%)124.2 W✓ PASS (≤3%)
1 AWG42.41 mm²130 A1.23 V (0.51%)238.8 V2.03 V (0.85%)98.4 W✓ PASS (≤3%)
1/0 AWG53.49 mm²150 A0.98 V (0.41%)239.0 V1.61 V (0.67%)78.0 W✓ PASS (≤3%)
2/0 AWG67.43 mm²175 A0.77 V (0.32%)239.2 V1.28 V (0.53%)61.9 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A0.61 V (0.26%)239.4 V1.01 V (0.42%)49.1 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A0.49 V (0.2%)239.5 V0.8 V (0.33%)38.9 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A0.41 V (0.17%)239.6 V0.68 V (0.28%)32.9 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A0.34 V (0.14%)239.7 V0.57 V (0.24%)27.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A0.29 V (0.12%)239.7 V0.49 V (0.2%)23.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A0.26 V (0.11%)239.7 V0.42 V (0.18%)20.6 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A0.21 V (0.09%)239.8 V0.34 V (0.14%)16.5 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A0.17 V (0.07%)239.8 V0.28 V (0.12%)13.7 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A0.14 V (0.06%)239.9 V0.23 V (0.09%)11.0 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.1 V (0.04%)239.9 V0.17 V (0.07%)8.2 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 80 amps at 50 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 80A load over 50 feet one-way at 240V (1-Phase), you need 4 AWG copper wire. This produces a voltage drop of 2.47V (1.03%) and delivers 237.5V at the load.

What size aluminum wire is required for 80 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 2 AWG to maintain voltage drop at 2.56V (1.07%).

What breaker size is needed for a 80A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (80A × 1.25 = 100.0A), which corresponds to a standard 100A circuit breaker.