🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 200 Feet (480V Three-Phase (US Heavy Industrial))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 200 ft (61.0 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.28%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.41V (0.92%)
Voltage at Load End478.7 VLoss: 1.34 V (1390.3 W)
Power & Breaker (125%)498.83 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 200 Feet (480V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A651.79 V (135.79%)0.0 V1075.15 V (223.99%)677359.4 WDrop/Amp High
12 AWG3.31 mm²20 A409.58 V (85.33%)70.4 V675.62 V (140.75%)425651.8 WDrop/Amp High
10 AWG5.26 mm²30 A257.74 V (53.7%)222.3 V425.15 V (88.57%)267853.1 WDrop/Amp High
8 AWG8.37 mm²50 A161.97 V (33.74%)318.0 V267.18 V (55.66%)168328.3 WDrop/Amp High
6 AWG13.3 mm²65 A101.93 V (21.24%)378.1 V168.14 V (35.03%)105932.9 WDrop/Amp High
4 AWG21.15 mm²85 A64.1 V (13.35%)415.9 V105.74 V (22.03%)66615.0 WDrop/Amp High
3 AWG26.67 mm²100 A50.83 V (10.59%)429.2 V83.85 V (17.47%)52827.4 WDrop/Amp High
2 AWG33.62 mm²115 A40.32 V (8.4%)439.7 V66.52 V (13.86%)41906.8 WDrop/Amp High
1 AWG42.41 mm²130 A31.97 V (6.66%)448.0 V52.73 V (10.99%)33221.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.35 V (5.28%)454.7 V41.81 V (8.71%)26339.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.11 V (4.19%)459.9 V33.16 V (6.91%)20894.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A15.95 V (3.32%)464.1 V26.31 V (5.48%)16573.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.65 V (2.63%)467.4 V20.86 V (4.35%)13142.8 WDrop/Amp High
250 kcmil126.7 mm²255 A10.7 V (2.23%)469.3 V17.65 V (3.68%)11120.0 WDrop/Amp High
300 kcmil152.0 mm²285 A8.92 V (1.86%)471.1 V14.71 V (3.07%)9269.1 WDrop/Amp High
350 kcmil177.3 mm²310 A7.65 V (1.59%)472.4 V12.61 V (2.63%)7946.5 WDrop/Amp High
400 kcmil202.7 mm²335 A6.69 V (1.39%)473.3 V11.03 V (2.3%)6950.7 WDrop/Amp High
500 kcmil253.4 mm²380 A5.35 V (1.11%)474.6 V8.83 V (1.84%)5560.0 WDrop/Amp High
600 kcmil304.0 mm²420 A4.46 V (0.93%)475.5 V7.36 V (1.53%)4634.6 WDrop/Amp High
750 kcmil380.0 mm²475 A3.57 V (0.74%)476.4 V5.89 V (1.23%)3707.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.68 V (0.56%)477.3 V4.41 V (0.92%)2780.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 200 feet (480V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 200 feet one-way at 480V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.34V (0.28%) and delivers 478.7V at the load.

What size aluminum wire is required for 600 amps at 200 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.41V (0.92%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.