⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 275 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 275 ft (83.8 m) one-way run.

Copper Wire (≤3% Drop)12× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.95%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 7.01V (58.39%)
Voltage at Load End11.7 VLoss: 0.35 V (212.4 W)
Power & Breaker (125%)7.2 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 275 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1034.85 V (8623.79%)0.0 V1707.03 V (14225.22%)620912.8 WDrop/Amp High
12 AWG3.31 mm²20 A650.3 V (5419.18%)0.0 V1072.69 V (8939.11%)390180.8 WDrop/Amp High
10 AWG5.26 mm²30 A409.22 V (3410.17%)0.0 V675.02 V (5625.18%)245532.0 WDrop/Amp High
8 AWG8.37 mm²50 A257.17 V (2143.07%)0.0 V424.21 V (3535.06%)154300.9 WDrop/Amp High
6 AWG13.3 mm²65 A161.84 V (1348.68%)0.0 V266.96 V (2224.7%)97105.2 WDrop/Amp High
4 AWG21.15 mm²85 A101.77 V (848.11%)0.0 V167.88 V (1398.98%)61063.8 WDrop/Amp High
3 AWG26.67 mm²100 A80.71 V (672.57%)0.0 V133.13 V (1109.43%)48425.1 WDrop/Amp High
2 AWG33.62 mm²115 A64.02 V (533.54%)0.0 V105.61 V (880.09%)38414.6 WDrop/Amp High
1 AWG42.41 mm²130 A50.75 V (422.95%)0.0 V83.72 V (697.68%)30452.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A40.24 V (335.34%)0.0 V66.38 V (553.16%)24144.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A31.92 V (266.02%)0.0 V52.66 V (438.8%)19153.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A25.32 V (211.0%)0.0 V41.77 V (348.06%)15192.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A20.08 V (167.33%)0.0 V33.12 V (276.01%)12047.6 WDrop/Amp High
250 kcmil126.7 mm²255 A16.99 V (141.57%)0.0 V28.02 V (233.53%)10193.4 WDrop/Amp High
300 kcmil152.0 mm²285 A14.16 V (118.01%)0.0 V23.36 V (194.66%)8496.7 WDrop/Amp High
350 kcmil177.3 mm²310 A12.14 V (101.17%)0.0 V20.03 V (166.88%)7284.3 WDrop/Amp High
400 kcmil202.7 mm²335 A10.62 V (88.49%)1.4 V17.52 V (145.97%)6371.5 WDrop/Amp High
500 kcmil253.4 mm²380 A8.49 V (70.79%)3.5 V14.01 V (116.77%)5096.7 WDrop/Amp High
600 kcmil304.0 mm²420 A7.08 V (59.0%)4.9 V11.68 V (97.33%)4248.4 WDrop/Amp High
750 kcmil380.0 mm²475 A5.66 V (47.2%)6.3 V9.34 V (77.86%)3398.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A4.25 V (35.4%)7.8 V7.01 V (58.39%)2548.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 275 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 275 feet one-way at 12V (DC), you need 12× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.35V (2.95%) and delivers 11.7V at the load.

What size aluminum wire is required for 600 amps at 275 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 7.01V (58.39%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.