🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 30 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.1%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.76V (0.32%)
Voltage at Load End239.8 VLoss: 0.23 V (139.1 W)
Power & Breaker (125%)144.0 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A112.89 V (47.04%)127.1 V186.22 V (77.59%)67735.9 WDrop/Amp High
12 AWG3.31 mm²20 A70.94 V (29.56%)169.1 V117.02 V (48.76%)42565.2 WDrop/Amp High
10 AWG5.26 mm²30 A44.64 V (18.6%)195.4 V73.64 V (30.68%)26785.3 WDrop/Amp High
8 AWG8.37 mm²50 A28.05 V (11.69%)211.9 V46.28 V (19.28%)16832.8 WDrop/Amp High
6 AWG13.3 mm²65 A17.66 V (7.36%)222.3 V29.12 V (12.13%)10593.3 WDrop/Amp High
4 AWG21.15 mm²85 A11.1 V (4.63%)228.9 V18.31 V (7.63%)6661.5 WDrop/Amp High
3 AWG26.67 mm²100 A8.8 V (3.67%)231.2 V14.52 V (6.05%)5282.7 WDrop/Amp High
2 AWG33.62 mm²115 A6.98 V (2.91%)233.0 V11.52 V (4.8%)4190.7 WDrop/Amp High
1 AWG42.41 mm²130 A5.54 V (2.31%)234.5 V9.13 V (3.81%)3322.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.39 V (1.83%)235.6 V7.24 V (3.02%)2634.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.48 V (1.45%)236.5 V5.74 V (2.39%)2089.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.76 V (1.15%)237.2 V4.56 V (1.9%)1657.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.19 V (0.91%)237.8 V3.61 V (1.51%)1314.3 WDrop/Amp High
250 kcmil126.7 mm²255 A1.85 V (0.77%)238.1 V3.06 V (1.27%)1112.0 WDrop/Amp High
300 kcmil152.0 mm²285 A1.54 V (0.64%)238.5 V2.55 V (1.06%)926.9 WDrop/Amp High
350 kcmil177.3 mm²310 A1.32 V (0.55%)238.7 V2.18 V (0.91%)794.6 WDrop/Amp High
400 kcmil202.7 mm²335 A1.16 V (0.48%)238.8 V1.91 V (0.8%)695.1 WDrop/Amp High
500 kcmil253.4 mm²380 A0.93 V (0.39%)239.1 V1.53 V (0.64%)556.0 WDrop/Amp High
600 kcmil304.0 mm²420 A0.77 V (0.32%)239.2 V1.27 V (0.53%)463.5 WDrop/Amp High
750 kcmil380.0 mm²475 A0.62 V (0.26%)239.4 V1.02 V (0.42%)370.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.46 V (0.19%)239.5 V0.76 V (0.32%)278.1 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 30 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.23V (0.1%) and delivers 239.8V at the load.

What size aluminum wire is required for 600 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.76V (0.32%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.