⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 80 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.26%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.04V (0.85%)
Voltage at Load End239.4 VLoss: 0.62 V (370.8 W)
Power & Breaker (125%)144.0 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A301.05 V (125.44%)0.0 V496.59 V (206.91%)180629.2 WDrop/Amp High
12 AWG3.31 mm²20 A189.18 V (78.82%)50.8 V312.06 V (130.02%)113507.2 WDrop/Amp High
10 AWG5.26 mm²30 A119.05 V (49.6%)121.0 V196.37 V (81.82%)71427.5 WDrop/Amp High
8 AWG8.37 mm²50 A74.81 V (31.17%)165.2 V123.41 V (51.42%)44887.5 WDrop/Amp High
6 AWG13.3 mm²65 A47.08 V (19.62%)192.9 V77.66 V (32.36%)28248.8 WDrop/Amp High
4 AWG21.15 mm²85 A29.61 V (12.34%)210.4 V48.84 V (20.35%)17764.0 WDrop/Amp High
3 AWG26.67 mm²100 A23.48 V (9.78%)216.5 V38.73 V (16.14%)14087.3 WDrop/Amp High
2 AWG33.62 mm²115 A18.63 V (7.76%)221.4 V30.72 V (12.8%)11175.2 WDrop/Amp High
1 AWG42.41 mm²130 A14.76 V (6.15%)225.2 V24.36 V (10.15%)8859.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.71 V (4.88%)228.3 V19.31 V (8.05%)7023.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.29 V (3.87%)230.7 V15.32 V (6.38%)5571.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.37 V (3.07%)232.6 V12.15 V (5.06%)4419.6 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.84 V (2.43%)234.2 V9.64 V (4.01%)3504.7 WDrop/Amp High
250 kcmil126.7 mm²255 A4.94 V (2.06%)235.1 V8.15 V (3.4%)2965.3 WDrop/Amp High
300 kcmil152.0 mm²285 A4.12 V (1.72%)235.9 V6.8 V (2.83%)2471.8 WDrop/Amp High
350 kcmil177.3 mm²310 A3.53 V (1.47%)236.5 V5.83 V (2.43%)2119.1 WDrop/Amp High
400 kcmil202.7 mm²335 A3.09 V (1.29%)236.9 V5.1 V (2.12%)1853.5 WDrop/Amp High
500 kcmil253.4 mm²380 A2.47 V (1.03%)237.5 V4.08 V (1.7%)1482.7 WDrop/Amp High
600 kcmil304.0 mm²420 A2.06 V (0.86%)237.9 V3.4 V (1.42%)1235.9 WDrop/Amp High
750 kcmil380.0 mm²475 A1.65 V (0.69%)238.4 V2.72 V (1.13%)988.7 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.24 V (0.51%)238.8 V2.04 V (0.85%)741.5 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 80 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.62V (0.26%) and delivers 239.4V at the load.

What size aluminum wire is required for 600 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.04V (0.85%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.