🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

600 Amp Wire Size at 175 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 600 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.56%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.46V (1.86%)
Voltage at Load End238.7 VLoss: 1.35 V (811.0 W)
Power & Breaker (125%)144.0 kW800A Breaker Recommended

All AWG & kcmil Wire Gauges for 600 Amps at 175 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A658.54 V (274.39%)0.0 V1086.29 V (452.62%)395126.3 WDrop/Amp High
12 AWG3.31 mm²20 A413.83 V (172.43%)0.0 V682.62 V (284.43%)248296.9 WDrop/Amp High
10 AWG5.26 mm²30 A260.41 V (108.51%)0.0 V429.56 V (178.98%)156247.7 WDrop/Amp High
8 AWG8.37 mm²50 A163.65 V (68.19%)76.3 V269.95 V (112.48%)98191.5 WDrop/Amp High
6 AWG13.3 mm²65 A102.99 V (42.91%)137.0 V169.89 V (70.79%)61794.2 WDrop/Amp High
4 AWG21.15 mm²85 A64.76 V (26.99%)175.2 V106.83 V (44.51%)38858.8 WDrop/Amp High
3 AWG26.67 mm²100 A51.36 V (21.4%)188.6 V84.72 V (35.3%)30816.0 WDrop/Amp High
2 AWG33.62 mm²115 A40.74 V (16.98%)199.3 V67.21 V (28.0%)24445.6 WDrop/Amp High
1 AWG42.41 mm²130 A32.3 V (13.46%)207.7 V53.28 V (22.2%)19379.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.61 V (10.67%)214.4 V42.24 V (17.6%)15364.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.31 V (8.46%)219.7 V33.51 V (13.96%)12188.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.11 V (6.71%)223.9 V26.58 V (11.07%)9667.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.78 V (5.32%)227.2 V21.08 V (8.78%)7666.6 WDrop/Amp High
250 kcmil126.7 mm²255 A10.81 V (4.5%)229.2 V17.83 V (7.43%)6486.7 WDrop/Amp High
300 kcmil152.0 mm²285 A9.01 V (3.75%)231.0 V14.87 V (6.19%)5407.0 WDrop/Amp High
350 kcmil177.3 mm²310 A7.73 V (3.22%)232.3 V12.74 V (5.31%)4635.4 WDrop/Amp High
400 kcmil202.7 mm²335 A6.76 V (2.82%)233.2 V11.15 V (4.64%)4054.6 WDrop/Amp High
500 kcmil253.4 mm²380 A5.41 V (2.25%)234.6 V8.92 V (3.72%)3243.3 WDrop/Amp High
600 kcmil304.0 mm²420 A4.51 V (1.88%)235.5 V7.43 V (3.1%)2703.5 WDrop/Amp High
750 kcmil380.0 mm²475 A3.6 V (1.5%)236.4 V5.95 V (2.48%)2162.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.7 V (1.13%)237.3 V4.46 V (1.86%)1622.0 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 600 amps at 175 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 600A load over 175 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.35V (0.56%) and delivers 238.7V at the load.

What size aluminum wire is required for 600 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.46V (1.86%).

What breaker size is needed for a 600A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (600A × 1.25 = 750.0A), which corresponds to a standard 800A circuit breaker.