🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 1000 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)5× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 27.6V (23.0%)
Voltage at Load End116.7 VLoss: 3.35 V (2175.5 W)
Power & Breaker (125%)78.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 1000 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4076.7 V (3397.25%)0.0 V6724.65 V (5603.88%)2649855.0 WDrop/Amp High
12 AWG3.31 mm²20 A2561.79 V (2134.83%)0.0 V4225.76 V (3521.47%)1665165.7 WDrop/Amp High
10 AWG5.26 mm²30 A1612.08 V (1343.4%)0.0 V2659.18 V (2215.98%)1047851.4 WDrop/Amp High
8 AWG8.37 mm²50 A1013.09 V (844.24%)0.0 V1671.12 V (1392.6%)658506.4 WDrop/Amp High
6 AWG13.3 mm²65 A637.56 V (531.3%)0.0 V1051.67 V (876.4%)414413.4 WDrop/Amp High
4 AWG21.15 mm²85 A400.92 V (334.1%)0.0 V661.34 V (551.11%)260600.4 WDrop/Amp High
3 AWG26.67 mm²100 A317.94 V (264.95%)0.0 V524.46 V (437.05%)206662.9 WDrop/Amp High
2 AWG33.62 mm²115 A252.22 V (210.18%)0.0 V416.04 V (346.7%)163941.1 WDrop/Amp High
1 AWG42.41 mm²130 A199.94 V (166.62%)0.0 V329.81 V (274.84%)129962.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A158.53 V (132.1%)0.0 V261.49 V (217.91%)103041.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A125.75 V (104.79%)0.0 V207.43 V (172.86%)81739.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A99.75 V (83.12%)20.3 V164.54 V (137.11%)64835.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A79.1 V (65.92%)40.9 V130.48 V (108.73%)51415.1 WDrop/Amp High
250 kcmil126.7 mm²255 A66.93 V (55.77%)53.1 V110.4 V (92.0%)43502.0 WDrop/Amp High
300 kcmil152.0 mm²285 A55.79 V (46.49%)64.2 V92.02 V (76.68%)36261.2 WDrop/Amp High
350 kcmil177.3 mm²310 A47.83 V (39.85%)72.2 V78.89 V (65.74%)31086.8 WDrop/Amp High
400 kcmil202.7 mm²335 A41.83 V (34.86%)78.2 V69.0 V (57.5%)27191.4 WDrop/Amp High
500 kcmil253.4 mm²380 A33.46 V (27.89%)86.5 V55.2 V (46.0%)21751.0 WDrop/Amp High
600 kcmil304.0 mm²420 A27.89 V (23.24%)92.1 V46.01 V (38.34%)18130.6 WDrop/Amp High
750 kcmil380.0 mm²475 A22.31 V (18.6%)97.7 V36.81 V (30.67%)14504.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A16.73 V (13.95%)103.3 V27.6 V (23.0%)10877.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 1000 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 1000 feet one-way at 120V (1-Phase), you need 5× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.35V (2.79%) and delivers 116.7V at the load.

What size aluminum wire is required for 650 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 27.6V (23.0%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.