🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 80 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.56%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.21V (1.84%)
Voltage at Load End119.3 VLoss: 0.67 V (435.1 W)
Power & Breaker (125%)78.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 80 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A326.14 V (271.78%)0.0 V537.97 V (448.31%)211988.4 WDrop/Amp High
12 AWG3.31 mm²20 A204.94 V (170.79%)0.0 V338.06 V (281.72%)133213.3 WDrop/Amp High
10 AWG5.26 mm²30 A128.97 V (107.47%)0.0 V212.73 V (177.28%)83828.1 WDrop/Amp High
8 AWG8.37 mm²50 A81.05 V (67.54%)39.0 V133.69 V (111.41%)52680.5 WDrop/Amp High
6 AWG13.3 mm²65 A51.0 V (42.5%)69.0 V84.13 V (70.11%)33153.1 WDrop/Amp High
4 AWG21.15 mm²85 A32.07 V (26.73%)87.9 V52.91 V (44.09%)20848.0 WDrop/Amp High
3 AWG26.67 mm²100 A25.44 V (21.2%)94.6 V41.96 V (34.96%)16533.0 WDrop/Amp High
2 AWG33.62 mm²115 A20.18 V (16.81%)99.8 V33.28 V (27.74%)13115.3 WDrop/Amp High
1 AWG42.41 mm²130 A16.0 V (13.33%)104.0 V26.38 V (21.99%)10397.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.68 V (10.57%)107.3 V20.92 V (17.43%)8243.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.06 V (8.38%)109.9 V16.59 V (13.83%)6539.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.98 V (6.65%)112.0 V13.16 V (10.97%)5186.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.33 V (5.27%)113.7 V10.44 V (8.7%)4113.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.35 V (4.46%)114.6 V8.83 V (7.36%)3480.2 WDrop/Amp High
300 kcmil152.0 mm²285 A4.46 V (3.72%)115.5 V7.36 V (6.13%)2900.9 WDrop/Amp High
350 kcmil177.3 mm²310 A3.83 V (3.19%)116.2 V6.31 V (5.26%)2486.9 WDrop/Amp High
400 kcmil202.7 mm²335 A3.35 V (2.79%)116.7 V5.52 V (4.6%)2175.3 WDrop/Amp High
500 kcmil253.4 mm²380 A2.68 V (2.23%)117.3 V4.42 V (3.68%)1740.1 WDrop/Amp High
600 kcmil304.0 mm²420 A2.23 V (1.86%)117.8 V3.68 V (3.07%)1450.4 WDrop/Amp High
750 kcmil380.0 mm²475 A1.79 V (1.49%)118.2 V2.94 V (2.45%)1160.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.34 V (1.12%)118.7 V2.21 V (1.84%)870.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 80 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 80 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.67V (0.56%) and delivers 119.3V at the load.

What size aluminum wire is required for 650 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.21V (1.84%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.