⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 125 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 125 ft (38.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.87%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.45V (2.88%)
Voltage at Load End119.0 VLoss: 1.04 V (679.9 W)
Power & Breaker (125%)78.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 125 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A509.59 V (424.66%)0.0 V840.58 V (700.48%)331231.9 WDrop/Amp High
12 AWG3.31 mm²20 A320.22 V (266.85%)0.0 V528.22 V (440.18%)208145.7 WDrop/Amp High
10 AWG5.26 mm²30 A201.51 V (167.92%)0.0 V332.4 V (277.0%)130981.4 WDrop/Amp High
8 AWG8.37 mm²50 A126.64 V (105.53%)0.0 V208.89 V (174.07%)82313.3 WDrop/Amp High
6 AWG13.3 mm²65 A79.69 V (66.41%)40.3 V131.46 V (109.55%)51801.7 WDrop/Amp High
4 AWG21.15 mm²85 A50.12 V (41.76%)69.9 V82.67 V (68.89%)32575.0 WDrop/Amp High
3 AWG26.67 mm²100 A39.74 V (33.12%)80.3 V65.56 V (54.63%)25832.9 WDrop/Amp High
2 AWG33.62 mm²115 A31.53 V (26.27%)88.5 V52.01 V (43.34%)20492.6 WDrop/Amp High
1 AWG42.41 mm²130 A24.99 V (20.83%)95.0 V41.23 V (34.36%)16245.3 WDrop/Amp High
1/0 AWG53.49 mm²150 A19.82 V (16.51%)100.2 V32.69 V (27.24%)12880.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A15.72 V (13.1%)104.3 V25.93 V (21.61%)10217.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A12.47 V (10.39%)107.5 V20.57 V (17.14%)8104.5 WDrop/Amp High
4/0 AWG107.2 mm²230 A9.89 V (8.24%)110.1 V16.31 V (13.59%)6426.9 WDrop/Amp High
250 kcmil126.7 mm²255 A8.37 V (6.97%)111.6 V13.8 V (11.5%)5437.7 WDrop/Amp High
300 kcmil152.0 mm²285 A6.97 V (5.81%)113.0 V11.5 V (9.59%)4532.6 WDrop/Amp High
350 kcmil177.3 mm²310 A5.98 V (4.98%)114.0 V9.86 V (8.22%)3885.9 WDrop/Amp High
400 kcmil202.7 mm²335 A5.23 V (4.36%)114.8 V8.63 V (7.19%)3398.9 WDrop/Amp High
500 kcmil253.4 mm²380 A4.18 V (3.49%)115.8 V6.9 V (5.75%)2718.9 WDrop/Amp High
600 kcmil304.0 mm²420 A3.49 V (2.91%)116.5 V5.75 V (4.79%)2266.3 WDrop/Amp High
750 kcmil380.0 mm²475 A2.79 V (2.32%)117.2 V4.6 V (3.83%)1813.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.09 V (1.74%)117.9 V3.45 V (2.88%)1359.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 125 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 125 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.04V (0.87%) and delivers 119.0V at the load.

What size aluminum wire is required for 650 amps at 125 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.45V (2.88%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.