🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 1000 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.32%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 27.6V (11.5%)
Voltage at Load End234.4 VLoss: 5.58 V (3625.9 W)
Power & Breaker (125%)156.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 1000 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A4076.7 V (1698.62%)0.0 V6724.65 V (2801.94%)2649855.0 WDrop/Amp High
12 AWG3.31 mm²20 A2561.79 V (1067.41%)0.0 V4225.76 V (1760.73%)1665165.7 WDrop/Amp High
10 AWG5.26 mm²30 A1612.08 V (671.7%)0.0 V2659.18 V (1107.99%)1047851.4 WDrop/Amp High
8 AWG8.37 mm²50 A1013.09 V (422.12%)0.0 V1671.12 V (696.3%)658506.4 WDrop/Amp High
6 AWG13.3 mm²65 A637.56 V (265.65%)0.0 V1051.67 V (438.2%)414413.4 WDrop/Amp High
4 AWG21.15 mm²85 A400.92 V (167.05%)0.0 V661.34 V (275.56%)260600.4 WDrop/Amp High
3 AWG26.67 mm²100 A317.94 V (132.48%)0.0 V524.46 V (218.52%)206662.9 WDrop/Amp High
2 AWG33.62 mm²115 A252.22 V (105.09%)0.0 V416.04 V (173.35%)163941.1 WDrop/Amp High
1 AWG42.41 mm²130 A199.94 V (83.31%)40.1 V329.81 V (137.42%)129962.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A158.53 V (66.05%)81.5 V261.49 V (108.96%)103041.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A125.75 V (52.4%)114.2 V207.43 V (86.43%)81739.6 WDrop/Amp High
3/0 AWG85.01 mm²200 A99.75 V (41.56%)140.3 V164.54 V (68.56%)64835.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A79.1 V (32.96%)160.9 V130.48 V (54.37%)51415.1 WDrop/Amp High
250 kcmil126.7 mm²255 A66.93 V (27.89%)173.1 V110.4 V (46.0%)43502.0 WDrop/Amp High
300 kcmil152.0 mm²285 A55.79 V (23.24%)184.2 V92.02 V (38.34%)36261.2 WDrop/Amp High
350 kcmil177.3 mm²310 A47.83 V (19.93%)192.2 V78.89 V (32.87%)31086.8 WDrop/Amp High
400 kcmil202.7 mm²335 A41.83 V (17.43%)198.2 V69.0 V (28.75%)27191.4 WDrop/Amp High
500 kcmil253.4 mm²380 A33.46 V (13.94%)206.5 V55.2 V (23.0%)21751.0 WDrop/Amp High
600 kcmil304.0 mm²420 A27.89 V (11.62%)212.1 V46.01 V (19.17%)18130.6 WDrop/Amp High
750 kcmil380.0 mm²475 A22.31 V (9.3%)217.7 V36.81 V (15.34%)14504.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A16.73 V (6.97%)223.3 V27.6 V (11.5%)10877.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 1000 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 1000 feet one-way at 240V (1-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.58V (2.32%) and delivers 234.4V at the load.

What size aluminum wire is required for 650 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 27.6V (11.5%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.