🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 175 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 175 ft (53.3 m) one-way run.

Copper Wire (≤3% Drop)9× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.71%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.83V (40.26%)
Voltage at Load End11.7 VLoss: 0.33 V (211.5 W)
Power & Breaker (125%)7.8 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 175 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A713.42 V (5945.19%)0.0 V1176.81 V (9806.78%)463724.6 WDrop/Amp High
12 AWG3.31 mm²20 A448.31 V (3735.95%)0.0 V739.51 V (6162.57%)291404.0 WDrop/Amp High
10 AWG5.26 mm²30 A282.11 V (2350.95%)0.0 V465.36 V (3877.97%)183374.0 WDrop/Amp High
8 AWG8.37 mm²50 A177.29 V (1477.42%)0.0 V292.45 V (2437.05%)115238.6 WDrop/Amp High
6 AWG13.3 mm²65 A111.57 V (929.77%)0.0 V184.04 V (1533.69%)72522.3 WDrop/Amp High
4 AWG21.15 mm²85 A70.16 V (584.68%)0.0 V115.73 V (964.45%)45605.1 WDrop/Amp High
3 AWG26.67 mm²100 A55.64 V (463.67%)0.0 V91.78 V (764.83%)36166.0 WDrop/Amp High
2 AWG33.62 mm²115 A44.14 V (367.82%)0.0 V72.81 V (606.73%)28689.7 WDrop/Amp High
1 AWG42.41 mm²130 A34.99 V (291.58%)0.0 V57.72 V (480.97%)22743.4 WDrop/Amp High
1/0 AWG53.49 mm²150 A27.74 V (231.18%)0.0 V45.76 V (381.34%)18032.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A22.01 V (183.39%)0.0 V36.3 V (302.51%)14304.4 WDrop/Amp High
3/0 AWG85.01 mm²200 A17.46 V (145.47%)0.0 V28.79 V (239.95%)11346.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A13.84 V (115.35%)0.0 V22.83 V (190.28%)8997.6 WDrop/Amp High
250 kcmil126.7 mm²255 A11.71 V (97.6%)0.3 V19.32 V (161.0%)7612.8 WDrop/Amp High
300 kcmil152.0 mm²285 A9.76 V (81.36%)2.2 V16.1 V (134.2%)6345.7 WDrop/Amp High
350 kcmil177.3 mm²310 A8.37 V (69.75%)3.6 V13.81 V (115.05%)5440.2 WDrop/Amp High
400 kcmil202.7 mm²335 A7.32 V (61.01%)4.7 V12.08 V (100.63%)4758.5 WDrop/Amp High
500 kcmil253.4 mm²380 A5.86 V (48.8%)6.1 V9.66 V (80.5%)3806.4 WDrop/Amp High
600 kcmil304.0 mm²420 A4.88 V (40.68%)7.1 V8.05 V (67.1%)3172.9 WDrop/Amp High
750 kcmil380.0 mm²475 A3.91 V (32.54%)8.1 V6.44 V (53.68%)2538.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.93 V (24.4%)9.1 V4.83 V (40.26%)1903.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 175 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 175 feet one-way at 12V (DC), you need 9× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.33V (2.71%) and delivers 11.7V at the load.

What size aluminum wire is required for 650 amps at 175 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.83V (40.26%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.