🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 80 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)4× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.79%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.21V (18.4%)
Voltage at Load End11.7 VLoss: 0.34 V (217.6 W)
Power & Breaker (125%)7.8 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 80 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A326.14 V (2717.8%)0.0 V537.97 V (4483.1%)211988.4 WDrop/Amp High
12 AWG3.31 mm²20 A204.94 V (1707.86%)0.0 V338.06 V (2817.17%)133213.3 WDrop/Amp High
10 AWG5.26 mm²30 A128.97 V (1074.72%)0.0 V212.73 V (1772.78%)83828.1 WDrop/Amp High
8 AWG8.37 mm²50 A81.05 V (675.39%)0.0 V133.69 V (1114.08%)52680.5 WDrop/Amp High
6 AWG13.3 mm²65 A51.0 V (425.04%)0.0 V84.13 V (701.12%)33153.1 WDrop/Amp High
4 AWG21.15 mm²85 A32.07 V (267.28%)0.0 V52.91 V (440.89%)20848.0 WDrop/Amp High
3 AWG26.67 mm²100 A25.44 V (211.96%)0.0 V41.96 V (349.64%)16533.0 WDrop/Amp High
2 AWG33.62 mm²115 A20.18 V (168.14%)0.0 V33.28 V (277.36%)13115.3 WDrop/Amp High
1 AWG42.41 mm²130 A16.0 V (133.29%)0.0 V26.38 V (219.87%)10397.0 WDrop/Amp High
1/0 AWG53.49 mm²150 A12.68 V (105.68%)0.0 V20.92 V (174.33%)8243.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A10.06 V (83.84%)1.9 V16.59 V (138.29%)6539.2 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.98 V (66.5%)4.0 V13.16 V (109.69%)5186.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A6.33 V (52.73%)5.7 V10.44 V (86.99%)4113.2 WDrop/Amp High
250 kcmil126.7 mm²255 A5.35 V (44.62%)6.6 V8.83 V (73.6%)3480.2 WDrop/Amp High
300 kcmil152.0 mm²285 A4.46 V (37.19%)7.5 V7.36 V (61.35%)2900.9 WDrop/Amp High
350 kcmil177.3 mm²310 A3.83 V (31.88%)8.2 V6.31 V (52.59%)2486.9 WDrop/Amp High
400 kcmil202.7 mm²335 A3.35 V (27.89%)8.7 V5.52 V (46.0%)2175.3 WDrop/Amp High
500 kcmil253.4 mm²380 A2.68 V (22.31%)9.3 V4.42 V (36.8%)1740.1 WDrop/Amp High
600 kcmil304.0 mm²420 A2.23 V (18.6%)9.8 V3.68 V (30.67%)1450.4 WDrop/Amp High
750 kcmil380.0 mm²475 A1.79 V (14.88%)10.2 V2.94 V (24.54%)1160.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.34 V (11.16%)10.7 V2.21 V (18.4%)870.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 80 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 80 feet one-way at 12V (DC), you need 4× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.34V (2.79%) and delivers 11.7V at the load.

What size aluminum wire is required for 650 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.21V (18.4%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.