⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 20 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 20 ft (6.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.4%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.55V (4.6%)
Voltage at Load End11.8 VLoss: 0.17 V (108.8 W)
Power & Breaker (125%)7.8 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 20 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A81.53 V (679.45%)0.0 V134.49 V (1120.77%)52997.1 WDrop/Amp High
12 AWG3.31 mm²20 A51.24 V (426.97%)0.0 V84.52 V (704.29%)33303.3 WDrop/Amp High
10 AWG5.26 mm²30 A32.24 V (268.68%)0.0 V53.18 V (443.2%)20957.0 WDrop/Amp High
8 AWG8.37 mm²50 A20.26 V (168.85%)0.0 V33.42 V (278.52%)13170.1 WDrop/Amp High
6 AWG13.3 mm²65 A12.75 V (106.26%)0.0 V21.03 V (175.28%)8288.3 WDrop/Amp High
4 AWG21.15 mm²85 A8.02 V (66.82%)4.0 V13.23 V (110.22%)5212.0 WDrop/Amp High
3 AWG26.67 mm²100 A6.36 V (52.99%)5.6 V10.49 V (87.41%)4133.3 WDrop/Amp High
2 AWG33.62 mm²115 A5.04 V (42.04%)7.0 V8.32 V (69.34%)3278.8 WDrop/Amp High
1 AWG42.41 mm²130 A4.0 V (33.32%)8.0 V6.6 V (54.97%)2599.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A3.17 V (26.42%)8.8 V5.23 V (43.58%)2060.8 WDrop/Amp High
2/0 AWG67.43 mm²175 A2.52 V (20.96%)9.5 V4.15 V (34.57%)1634.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A1.99 V (16.62%)10.0 V3.29 V (27.42%)1296.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A1.58 V (13.18%)10.4 V2.61 V (21.75%)1028.3 WDrop/Amp High
250 kcmil126.7 mm²255 A1.34 V (11.15%)10.7 V2.21 V (18.4%)870.0 WDrop/Amp High
300 kcmil152.0 mm²285 A1.12 V (9.3%)10.9 V1.84 V (15.34%)725.2 WDrop/Amp High
350 kcmil177.3 mm²310 A0.96 V (7.97%)11.0 V1.58 V (13.15%)621.7 WDrop/Amp High
400 kcmil202.7 mm²335 A0.84 V (6.97%)11.2 V1.38 V (11.5%)543.8 WDrop/Amp High
500 kcmil253.4 mm²380 A0.67 V (5.58%)11.3 V1.1 V (9.2%)435.0 WDrop/Amp High
600 kcmil304.0 mm²420 A0.56 V (4.65%)11.4 V0.92 V (7.67%)362.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.45 V (3.72%)11.6 V0.74 V (6.13%)290.1 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.33 V (2.79%)11.7 V0.55 V (4.6%)217.6 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 20 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 20 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.17V (1.4%) and delivers 11.8V at the load.

What size aluminum wire is required for 650 amps at 20 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.55V (4.6%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.