🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 350 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.05%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 8.37V (3.49%)
Voltage at Load End237.5 VLoss: 2.54 V (2855.4 W)
Power & Breaker (125%)270.2 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 350 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1235.68 V (514.87%)0.0 V2038.3 V (849.29%)1391173.9 WDrop/Amp High
12 AWG3.31 mm²20 A776.5 V (323.54%)0.0 V1280.87 V (533.69%)874212.0 WDrop/Amp High
10 AWG5.26 mm²30 A488.64 V (203.6%)0.0 V806.02 V (335.84%)550122.0 WDrop/Amp High
8 AWG8.37 mm²50 A307.08 V (127.95%)0.0 V506.53 V (211.05%)345715.8 WDrop/Amp High
6 AWG13.3 mm²65 A193.25 V (80.52%)46.8 V318.77 V (132.82%)217567.0 WDrop/Amp High
4 AWG21.15 mm²85 A121.52 V (50.63%)118.5 V200.46 V (83.52%)136815.2 WDrop/Amp High
3 AWG26.67 mm²100 A96.37 V (40.15%)143.6 V158.97 V (66.24%)108498.0 WDrop/Amp High
2 AWG33.62 mm²115 A76.45 V (31.85%)163.6 V126.11 V (52.54%)86069.1 WDrop/Amp High
1 AWG42.41 mm²130 A60.6 V (25.25%)179.4 V99.97 V (41.65%)68230.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A48.05 V (20.02%)191.9 V79.26 V (33.03%)54096.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A38.12 V (15.88%)201.9 V62.88 V (26.2%)42913.3 WDrop/Amp High
3/0 AWG85.01 mm²200 A30.23 V (12.6%)209.8 V49.87 V (20.78%)34038.8 WDrop/Amp High
4/0 AWG107.2 mm²230 A23.98 V (9.99%)216.0 V39.55 V (16.48%)26992.9 WDrop/Amp High
250 kcmil126.7 mm²255 A20.29 V (8.45%)219.7 V33.46 V (13.94%)22838.5 WDrop/Amp High
300 kcmil152.0 mm²285 A16.91 V (7.05%)223.1 V27.89 V (11.62%)19037.1 WDrop/Amp High
350 kcmil177.3 mm²310 A14.5 V (6.04%)225.5 V23.91 V (9.96%)16320.6 WDrop/Amp High
400 kcmil202.7 mm²335 A12.68 V (5.28%)227.3 V20.92 V (8.71%)14275.5 WDrop/Amp High
500 kcmil253.4 mm²380 A10.14 V (4.23%)229.9 V16.73 V (6.97%)11419.3 WDrop/Amp High
600 kcmil304.0 mm²420 A8.45 V (3.52%)231.5 V13.95 V (5.81%)9518.6 WDrop/Amp High
750 kcmil380.0 mm²475 A6.76 V (2.82%)233.2 V11.16 V (4.65%)7614.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A5.07 V (2.11%)234.9 V8.37 V (3.49%)5710.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 350 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 350 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 2.54V (1.05%) and delivers 237.5V at the load.

What size aluminum wire is required for 650 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 8.37V (3.49%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.