⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 80 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.24%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.91V (0.8%)
Voltage at Load End239.4 VLoss: 0.58 V (652.6 W)
Power & Breaker (125%)270.2 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A282.44 V (117.68%)0.0 V465.9 V (194.12%)317982.6 WDrop/Amp High
12 AWG3.31 mm²20 A177.49 V (73.95%)62.5 V292.77 V (121.99%)199819.9 WDrop/Amp High
10 AWG5.26 mm²30 A111.69 V (46.54%)128.3 V184.23 V (76.76%)125742.2 WDrop/Amp High
8 AWG8.37 mm²50 A70.19 V (29.25%)169.8 V115.78 V (48.24%)79020.8 WDrop/Amp High
6 AWG13.3 mm²65 A44.17 V (18.4%)195.8 V72.86 V (30.36%)49729.6 WDrop/Amp High
4 AWG21.15 mm²85 A27.78 V (11.57%)212.2 V45.82 V (19.09%)31272.0 WDrop/Amp High
3 AWG26.67 mm²100 A22.03 V (9.18%)218.0 V36.34 V (15.14%)24799.5 WDrop/Amp High
2 AWG33.62 mm²115 A17.47 V (7.28%)222.5 V28.82 V (12.01%)19672.9 WDrop/Amp High
1 AWG42.41 mm²130 A13.85 V (5.77%)226.1 V22.85 V (9.52%)15595.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A10.98 V (4.58%)229.0 V18.12 V (7.55%)12365.0 WDrop/Amp High
2/0 AWG67.43 mm²175 A8.71 V (3.63%)231.3 V14.37 V (5.99%)9808.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A6.91 V (2.88%)233.1 V11.4 V (4.75%)7780.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.48 V (2.28%)234.5 V9.04 V (3.77%)6169.8 WDrop/Amp High
250 kcmil126.7 mm²255 A4.64 V (1.93%)235.4 V7.65 V (3.19%)5220.2 WDrop/Amp High
300 kcmil152.0 mm²285 A3.86 V (1.61%)236.1 V6.38 V (2.66%)4351.3 WDrop/Amp High
350 kcmil177.3 mm²310 A3.31 V (1.38%)236.7 V5.47 V (2.28%)3730.4 WDrop/Amp High
400 kcmil202.7 mm²335 A2.9 V (1.21%)237.1 V4.78 V (1.99%)3263.0 WDrop/Amp High
500 kcmil253.4 mm²380 A2.32 V (0.97%)237.7 V3.82 V (1.59%)2610.1 WDrop/Amp High
600 kcmil304.0 mm²420 A1.93 V (0.81%)238.1 V3.19 V (1.33%)2175.7 WDrop/Amp High
750 kcmil380.0 mm²475 A1.55 V (0.64%)238.5 V2.55 V (1.06%)1740.5 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.16 V (0.48%)238.8 V1.91 V (0.8%)1305.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 80 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.58V (0.24%) and delivers 239.4V at the load.

What size aluminum wire is required for 650 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.91V (0.8%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.