🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 50 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 50 ft (15.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.15%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.2V (0.5%)
Voltage at Load End239.6 VLoss: 0.36 V (407.9 W)
Power & Breaker (125%)270.2 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 50 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A176.53 V (73.55%)63.5 V291.19 V (121.33%)198739.1 WDrop/Amp High
12 AWG3.31 mm²20 A110.93 V (46.22%)129.1 V182.98 V (76.24%)124887.4 WDrop/Amp High
10 AWG5.26 mm²30 A69.81 V (29.09%)170.2 V115.15 V (47.98%)78588.9 WDrop/Amp High
8 AWG8.37 mm²50 A43.87 V (18.28%)196.1 V72.36 V (30.15%)49388.0 WDrop/Amp High
6 AWG13.3 mm²65 A27.61 V (11.5%)212.4 V45.54 V (18.97%)31081.0 WDrop/Amp High
4 AWG21.15 mm²85 A17.36 V (7.23%)222.6 V28.64 V (11.93%)19545.0 WDrop/Amp High
3 AWG26.67 mm²100 A13.77 V (5.74%)226.2 V22.71 V (9.46%)15499.7 WDrop/Amp High
2 AWG33.62 mm²115 A10.92 V (4.55%)229.1 V18.02 V (7.51%)12295.6 WDrop/Amp High
1 AWG42.41 mm²130 A8.66 V (3.61%)231.3 V14.28 V (5.95%)9747.2 WDrop/Amp High
1/0 AWG53.49 mm²150 A6.86 V (2.86%)233.1 V11.32 V (4.72%)7728.1 WDrop/Amp High
2/0 AWG67.43 mm²175 A5.45 V (2.27%)234.6 V8.98 V (3.74%)6130.5 WDrop/Amp High
3/0 AWG85.01 mm²200 A4.32 V (1.8%)235.7 V7.12 V (2.97%)4862.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A3.43 V (1.43%)236.6 V5.65 V (2.35%)3856.1 WDrop/Amp High
250 kcmil126.7 mm²255 A2.9 V (1.21%)237.1 V4.78 V (1.99%)3262.6 WDrop/Amp High
300 kcmil152.0 mm²285 A2.42 V (1.01%)237.6 V3.98 V (1.66%)2719.6 WDrop/Amp High
350 kcmil177.3 mm²310 A2.07 V (0.86%)237.9 V3.42 V (1.42%)2331.5 WDrop/Amp High
400 kcmil202.7 mm²335 A1.81 V (0.75%)238.2 V2.99 V (1.24%)2039.4 WDrop/Amp High
500 kcmil253.4 mm²380 A1.45 V (0.6%)238.6 V2.39 V (1.0%)1631.3 WDrop/Amp High
600 kcmil304.0 mm²420 A1.21 V (0.5%)238.8 V1.99 V (0.83%)1359.8 WDrop/Amp High
750 kcmil380.0 mm²475 A0.97 V (0.4%)239.0 V1.59 V (0.66%)1087.8 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.72 V (0.3%)239.3 V1.2 V (0.5%)815.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 50 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 50 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.36V (0.15%) and delivers 239.6V at the load.

What size aluminum wire is required for 650 amps at 50 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.2V (0.5%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.