🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 500 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 500 ft (152.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.51%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 11.95V (4.98%)
Voltage at Load End236.4 VLoss: 3.62 V (4079.1 W)
Power & Breaker (125%)270.2 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 500 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A1765.26 V (735.53%)0.0 V2911.86 V (1213.27%)1987391.2 WDrop/Amp High
12 AWG3.31 mm²20 A1109.29 V (462.2%)0.0 V1829.81 V (762.42%)1248874.3 WDrop/Amp High
10 AWG5.26 mm²30 A698.05 V (290.85%)0.0 V1151.46 V (479.77%)785888.6 WDrop/Amp High
8 AWG8.37 mm²50 A438.68 V (182.78%)0.0 V723.62 V (301.51%)493879.8 WDrop/Amp High
6 AWG13.3 mm²65 A276.07 V (115.03%)0.0 V455.39 V (189.75%)310810.1 WDrop/Amp High
4 AWG21.15 mm²85 A173.61 V (72.34%)66.4 V286.37 V (119.32%)195450.3 WDrop/Amp High
3 AWG26.67 mm²100 A137.67 V (57.36%)102.3 V227.1 V (94.62%)154997.1 WDrop/Amp High
2 AWG33.62 mm²115 A109.21 V (45.51%)130.8 V180.15 V (75.06%)122955.8 WDrop/Amp High
1 AWG42.41 mm²130 A86.58 V (36.07%)153.4 V142.81 V (59.51%)97471.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A68.64 V (28.6%)171.4 V113.23 V (47.18%)77281.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A54.45 V (22.69%)185.5 V89.82 V (37.43%)61304.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A43.19 V (18.0%)196.8 V71.25 V (29.69%)48626.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A34.25 V (14.27%)205.7 V56.5 V (23.54%)38561.3 WDrop/Amp High
250 kcmil126.7 mm²255 A28.98 V (12.07%)211.0 V47.8 V (19.92%)32626.5 WDrop/Amp High
300 kcmil152.0 mm²285 A24.16 V (10.07%)215.8 V39.85 V (16.6%)27195.9 WDrop/Amp High
350 kcmil177.3 mm²310 A20.71 V (8.63%)219.3 V34.16 V (14.23%)23315.1 WDrop/Amp High
400 kcmil202.7 mm²335 A18.11 V (7.55%)221.9 V29.88 V (12.45%)20393.6 WDrop/Amp High
500 kcmil253.4 mm²380 A14.49 V (6.04%)225.5 V23.9 V (9.96%)16313.2 WDrop/Amp High
600 kcmil304.0 mm²420 A12.08 V (5.03%)227.9 V19.92 V (8.3%)13597.9 WDrop/Amp High
750 kcmil380.0 mm²475 A9.66 V (4.03%)230.3 V15.94 V (6.64%)10878.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A7.25 V (3.02%)232.8 V11.95 V (4.98%)8158.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 500 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 500 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 3.62V (1.51%) and delivers 236.4V at the load.

What size aluminum wire is required for 650 amps at 500 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 11.95V (4.98%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.