🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

650 Amp Wire Size at 750 Feet (240V Split-Phase (US Dryer / EV / Subpanel))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 650 A load over a 750 ft (228.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.62%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 20.7V (8.63%)
Voltage at Load End233.7 VLoss: 6.28 V (4079.1 W)
Power & Breaker (125%)156.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 650 Amps at 750 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3057.53 V (1273.97%)0.0 V5043.49 V (2101.45%)1987391.3 WDrop/Amp High
12 AWG3.31 mm²20 A1921.35 V (800.56%)0.0 V3169.32 V (1320.55%)1248874.3 WDrop/Amp High
10 AWG5.26 mm²30 A1209.06 V (503.77%)0.0 V1994.38 V (830.99%)785888.6 WDrop/Amp High
8 AWG8.37 mm²50 A759.82 V (316.59%)0.0 V1253.34 V (522.22%)493879.8 WDrop/Amp High
6 AWG13.3 mm²65 A478.17 V (199.24%)0.0 V788.76 V (328.65%)310810.1 WDrop/Amp High
4 AWG21.15 mm²85 A300.69 V (125.29%)0.0 V496.0 V (206.67%)195450.3 WDrop/Amp High
3 AWG26.67 mm²100 A238.46 V (99.36%)1.5 V393.34 V (163.89%)154997.1 WDrop/Amp High
2 AWG33.62 mm²115 A189.16 V (78.82%)50.8 V312.03 V (130.01%)122955.8 WDrop/Amp High
1 AWG42.41 mm²130 A149.96 V (62.48%)90.0 V247.36 V (103.07%)97471.7 WDrop/Amp High
1/0 AWG53.49 mm²150 A118.89 V (49.54%)121.1 V196.12 V (81.72%)77281.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A94.31 V (39.3%)145.7 V155.58 V (64.82%)61304.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A74.81 V (31.17%)165.2 V123.4 V (51.42%)48626.9 WDrop/Amp High
4/0 AWG107.2 mm²230 A59.33 V (24.72%)180.7 V97.86 V (40.77%)38561.3 WDrop/Amp High
250 kcmil126.7 mm²255 A50.19 V (20.91%)189.8 V82.8 V (34.5%)32626.5 WDrop/Amp High
300 kcmil152.0 mm²285 A41.84 V (17.43%)198.2 V69.02 V (28.76%)27195.9 WDrop/Amp High
350 kcmil177.3 mm²310 A35.87 V (14.95%)204.1 V59.17 V (24.65%)23315.1 WDrop/Amp High
400 kcmil202.7 mm²335 A31.37 V (13.07%)208.6 V51.75 V (21.56%)20393.6 WDrop/Amp High
500 kcmil253.4 mm²380 A25.1 V (10.46%)214.9 V41.4 V (17.25%)16313.2 WDrop/Amp High
600 kcmil304.0 mm²420 A20.92 V (8.72%)219.1 V34.51 V (14.38%)13597.9 WDrop/Amp High
750 kcmil380.0 mm²475 A16.74 V (6.97%)223.3 V27.61 V (11.5%)10878.4 WDrop/Amp High
1000 kcmil506.7 mm²545 A12.55 V (5.23%)227.4 V20.7 V (8.63%)8158.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 650 amps at 750 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 650A load over 750 feet one-way at 240V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 6.28V (2.62%) and delivers 233.7V at the load.

What size aluminum wire is required for 650 amps at 750 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 20.7V (8.63%).

What breaker size is needed for a 650A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (650A × 1.25 = 812.5A), which corresponds to a standard 1000A circuit breaker.