🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 350 Feet (12V DC (Solar / Automotive / Marine))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 350 ft (106.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.63%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.04V (8.67%)
Voltage at Load End11.7 VLoss: 0.32 V (22.1 W)
Power & Breaker (125%)0.84 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 350 Feet (12V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A153.66 V (1280.5%)0.0 V253.47 V (2112.23%)10756.2 WDrop/Amp High
12 AWG3.31 mm²20 A96.56 V (804.67%)0.0 V159.28 V (1327.32%)6759.2 WDrop/Amp High
10 AWG5.26 mm²30 A60.76 V (506.36%)0.0 V100.23 V (835.25%)4253.4 WDrop/Amp High
8 AWG8.37 mm²50 A38.19 V (318.21%)0.0 V62.99 V (524.9%)2673.0 WDrop/Amp High
6 AWG13.3 mm²65 A24.03 V (200.26%)0.0 V39.64 V (330.33%)1682.2 WDrop/Amp High
4 AWG21.15 mm²85 A15.11 V (125.93%)0.0 V24.93 V (207.73%)1057.8 WDrop/Amp High
3 AWG26.67 mm²100 A11.98 V (99.87%)0.0 V19.77 V (164.73%)838.9 WDrop/Amp High
2 AWG33.62 mm²115 A9.51 V (79.22%)2.5 V15.68 V (130.68%)665.5 WDrop/Amp High
1 AWG42.41 mm²130 A7.54 V (62.8%)4.5 V12.43 V (103.59%)527.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.98 V (49.79%)6.0 V9.86 V (82.14%)418.3 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.74 V (39.5%)7.3 V7.82 V (65.16%)331.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.76 V (31.33%)8.2 V6.2 V (51.68%)263.2 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.98 V (24.85%)9.0 V4.92 V (40.98%)208.7 WDrop/Amp High
250 kcmil126.7 mm²255 A2.52 V (21.02%)9.5 V4.16 V (34.68%)176.6 WDrop/Amp High
300 kcmil152.0 mm²285 A2.1 V (17.52%)9.9 V3.47 V (28.9%)147.2 WDrop/Amp High
350 kcmil177.3 mm²310 A1.8 V (15.02%)10.2 V2.97 V (24.78%)126.2 WDrop/Amp High
400 kcmil202.7 mm²335 A1.58 V (13.14%)10.4 V2.6 V (21.67%)110.4 WDrop/Amp High
500 kcmil253.4 mm²380 A1.26 V (10.51%)10.7 V2.08 V (17.34%)88.3 WDrop/Amp High
600 kcmil304.0 mm²420 A1.05 V (8.76%)10.9 V1.73 V (14.45%)73.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.84 V (7.01%)11.2 V1.39 V (11.56%)58.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.63 V (5.26%)11.4 V1.04 V (8.67%)44.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 350 feet (12V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 350 feet one-way at 12V (DC), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.32V (2.63%) and delivers 11.7V at the load.

What size aluminum wire is required for 70 amps at 350 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.04V (8.67%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.