⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

70 Amp Wire Size at 600 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 70 A load over a 600 ft (182.9 m) one-way run.

Copper Wire (≤3% Drop)2/0 AWG67.43 mm² · Drop: 2.93%
Aluminum Wire (≤3% Drop)250 kcmilDrop: 6.18V (2.57%)
Voltage at Load End233.0 VLoss: 7.04 V (853.2 W)
Power & Breaker (125%)29.1 kW90A Breaker Recommended

All AWG & kcmil Wire Gauges for 70 Amps at 600 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A228.13 V (95.05%)11.9 V376.3 V (156.79%)27658.8 WDrop/Amp High
12 AWG3.31 mm²20 A143.35 V (59.73%)96.6 V236.47 V (98.53%)17380.8 WDrop/Amp High
10 AWG5.26 mm²30 A90.21 V (37.59%)149.8 V148.8 V (62.0%)10937.3 WDrop/Amp High
8 AWG8.37 mm²50 A56.69 V (23.62%)183.3 V93.51 V (38.96%)6873.4 WDrop/Amp High
6 AWG13.3 mm²65 A35.68 V (14.87%)204.3 V58.85 V (24.52%)4325.6 WDrop/Amp High
4 AWG21.15 mm²85 A22.44 V (9.35%)217.6 V37.01 V (15.42%)2720.1 WDrop/Amp High
3 AWG26.67 mm²100 A17.79 V (7.41%)222.2 V29.35 V (12.23%)2157.1 WDrop/Amp High
2 AWG33.62 mm²115 A14.11 V (5.88%)225.9 V23.28 V (9.7%)1711.2 WDrop/Amp High
1 AWG42.41 mm²130 A11.19 V (4.66%)228.8 V18.46 V (7.69%)1356.5 W~ ≤5%
1/0 AWG53.49 mm²150 A8.87 V (3.7%)231.1 V14.63 V (6.1%)1075.5 W~ ≤5%
2/0 AWG67.43 mm²175 A7.04 V (2.93%)233.0 V11.61 V (4.84%)853.2 W✓ PASS (≤3%)
3/0 AWG85.01 mm²200 A5.58 V (2.33%)234.4 V9.21 V (3.84%)676.7 W✓ PASS (≤3%)
4/0 AWG107.2 mm²230 A4.43 V (1.84%)235.6 V7.3 V (3.04%)536.7 W✓ PASS (≤3%)
250 kcmil126.7 mm²255 A3.75 V (1.56%)236.3 V6.18 V (2.57%)454.1 W✓ PASS (≤3%)
300 kcmil152.0 mm²285 A3.12 V (1.3%)236.9 V5.15 V (2.15%)378.5 W✓ PASS (≤3%)
350 kcmil177.3 mm²310 A2.68 V (1.12%)237.3 V4.41 V (1.84%)324.5 W✓ PASS (≤3%)
400 kcmil202.7 mm²335 A2.34 V (0.98%)237.7 V3.86 V (1.61%)283.8 W✓ PASS (≤3%)
500 kcmil253.4 mm²380 A1.87 V (0.78%)238.1 V3.09 V (1.29%)227.0 W✓ PASS (≤3%)
600 kcmil304.0 mm²420 A1.56 V (0.65%)238.4 V2.57 V (1.07%)189.2 W✓ PASS (≤3%)
750 kcmil380.0 mm²475 A1.25 V (0.52%)238.8 V2.06 V (0.86%)151.4 W✓ PASS (≤3%)
1000 kcmil506.7 mm²545 A0.94 V (0.39%)239.1 V1.54 V (0.64%)113.5 W✓ PASS (≤3%)

Frequently Asked Engineering Questions

What size copper wire do I need for 70 amps at 600 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 70A load over 600 feet one-way at 240V (3-Phase), you need 2/0 AWG copper wire. This produces a voltage drop of 7.04V (2.93%) and delivers 233.0V at the load.

What size aluminum wire is required for 70 amps at 600 feet?

Using aluminum conductors (75°C rating), you should use 250 kcmil to maintain voltage drop at 6.18V (2.57%).

What breaker size is needed for a 70A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (70A × 1.25 = 87.5A), which corresponds to a standard 90A circuit breaker.