🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 100 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 100 ft (30.5 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.33%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.57V (1.07%)
Voltage at Load End239.2 VLoss: 0.78 V (946.1 W)
Power & Breaker (125%)290.98 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 100 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A380.21 V (158.42%)0.0 V627.17 V (261.32%)460980.7 WDrop/Amp High
12 AWG3.31 mm²20 A238.92 V (99.55%)1.1 V394.11 V (164.21%)289679.7 WDrop/Amp High
10 AWG5.26 mm²30 A150.35 V (62.65%)89.7 V248.01 V (103.34%)182288.9 WDrop/Amp High
8 AWG8.37 mm²50 A94.48 V (39.37%)145.5 V155.86 V (64.94%)114556.7 WDrop/Amp High
6 AWG13.3 mm²65 A59.46 V (24.78%)180.5 V98.08 V (40.87%)72093.2 WDrop/Amp High
4 AWG21.15 mm²85 A37.39 V (15.58%)202.6 V61.68 V (25.7%)45335.2 WDrop/Amp High
3 AWG26.67 mm²100 A29.65 V (12.36%)210.3 V48.91 V (20.38%)35952.0 WDrop/Amp High
2 AWG33.62 mm²115 A23.52 V (9.8%)216.5 V38.8 V (16.17%)28519.9 WDrop/Amp High
1 AWG42.41 mm²130 A18.65 V (7.77%)221.4 V30.76 V (12.82%)22608.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A14.78 V (6.16%)225.2 V24.39 V (10.16%)17925.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A11.73 V (4.89%)228.3 V19.35 V (8.06%)14219.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A9.3 V (3.88%)230.7 V15.35 V (6.39%)11279.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A7.38 V (3.07%)232.6 V12.17 V (5.07%)8944.4 WDrop/Amp High
250 kcmil126.7 mm²255 A6.24 V (2.6%)233.8 V10.3 V (4.29%)7567.8 WDrop/Amp High
300 kcmil152.0 mm²285 A5.2 V (2.17%)234.8 V8.58 V (3.58%)6308.2 WDrop/Amp High
350 kcmil177.3 mm²310 A4.46 V (1.86%)235.5 V7.36 V (3.07%)5408.0 WDrop/Amp High
400 kcmil202.7 mm²335 A3.9 V (1.63%)236.1 V6.44 V (2.68%)4730.3 WDrop/Amp High
500 kcmil253.4 mm²380 A3.12 V (1.3%)236.9 V5.15 V (2.15%)3783.9 WDrop/Amp High
600 kcmil304.0 mm²420 A2.6 V (1.08%)237.4 V4.29 V (1.79%)3154.1 WDrop/Amp High
750 kcmil380.0 mm²475 A2.08 V (0.87%)237.9 V3.43 V (1.43%)2523.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.56 V (0.65%)238.4 V2.57 V (1.07%)1892.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 100 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 100 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.78V (0.33%) and delivers 239.2V at the load.

What size aluminum wire is required for 700 amps at 100 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.57V (1.07%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.