🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 40 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 40 ft (12.2 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.13%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 1.03V (0.43%)
Voltage at Load End239.7 VLoss: 0.31 V (378.4 W)
Power & Breaker (125%)290.98 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 40 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A152.08 V (63.37%)87.9 V250.87 V (104.53%)184392.3 WDrop/Amp High
12 AWG3.31 mm²20 A95.57 V (39.82%)144.4 V157.65 V (65.69%)115871.9 WDrop/Amp High
10 AWG5.26 mm²30 A60.14 V (25.06%)179.9 V99.2 V (41.33%)72915.6 WDrop/Amp High
8 AWG8.37 mm²50 A37.79 V (15.75%)202.2 V62.34 V (25.98%)45822.7 WDrop/Amp High
6 AWG13.3 mm²65 A23.78 V (9.91%)216.2 V39.23 V (16.35%)28837.3 WDrop/Amp High
4 AWG21.15 mm²85 A14.96 V (6.23%)225.0 V24.67 V (10.28%)18134.1 WDrop/Amp High
3 AWG26.67 mm²100 A11.86 V (4.94%)228.1 V19.57 V (8.15%)14380.8 WDrop/Amp High
2 AWG33.62 mm²115 A9.41 V (3.92%)230.6 V15.52 V (6.47%)11408.0 WDrop/Amp High
1 AWG42.41 mm²130 A7.46 V (3.11%)232.5 V12.3 V (5.13%)9043.5 WDrop/Amp High
1/0 AWG53.49 mm²150 A5.91 V (2.46%)234.1 V9.76 V (4.06%)7170.2 WDrop/Amp High
2/0 AWG67.43 mm²175 A4.69 V (1.95%)235.3 V7.74 V (3.22%)5687.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A3.72 V (1.55%)236.3 V6.14 V (2.56%)4511.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.95 V (1.23%)237.0 V4.87 V (2.03%)3577.8 WDrop/Amp High
250 kcmil126.7 mm²255 A2.5 V (1.04%)237.5 V4.12 V (1.72%)3027.1 WDrop/Amp High
300 kcmil152.0 mm²285 A2.08 V (0.87%)237.9 V3.43 V (1.43%)2523.3 WDrop/Amp High
350 kcmil177.3 mm²310 A1.78 V (0.74%)238.2 V2.94 V (1.23%)2163.2 WDrop/Amp High
400 kcmil202.7 mm²335 A1.56 V (0.65%)238.4 V2.57 V (1.07%)1892.1 WDrop/Amp High
500 kcmil253.4 mm²380 A1.25 V (0.52%)238.8 V2.06 V (0.86%)1513.6 WDrop/Amp High
600 kcmil304.0 mm²420 A1.04 V (0.43%)239.0 V1.72 V (0.72%)1261.6 WDrop/Amp High
750 kcmil380.0 mm²475 A0.83 V (0.35%)239.2 V1.37 V (0.57%)1009.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.62 V (0.26%)239.4 V1.03 V (0.43%)756.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 40 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 40 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.31V (0.13%) and delivers 239.7V at the load.

What size aluminum wire is required for 700 amps at 40 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 1.03V (0.43%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.