🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 80 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 80 ft (24.4 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.26%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 2.06V (0.86%)
Voltage at Load End239.4 VLoss: 0.62 V (757.0 W)
Power & Breaker (125%)290.98 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 80 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A304.17 V (126.74%)0.0 V501.74 V (209.06%)368784.6 WDrop/Amp High
12 AWG3.31 mm²20 A191.14 V (79.64%)48.9 V315.29 V (131.37%)231743.8 WDrop/Amp High
10 AWG5.26 mm²30 A120.28 V (50.12%)119.7 V198.4 V (82.67%)145831.2 WDrop/Amp High
8 AWG8.37 mm²50 A75.59 V (31.49%)164.4 V124.68 V (51.95%)91645.4 WDrop/Amp High
6 AWG13.3 mm²65 A47.57 V (19.82%)192.4 V78.47 V (32.69%)57674.6 WDrop/Amp High
4 AWG21.15 mm²85 A29.91 V (12.46%)210.1 V49.34 V (20.56%)36268.2 WDrop/Amp High
3 AWG26.67 mm²100 A23.72 V (9.88%)216.3 V39.13 V (16.3%)28761.6 WDrop/Amp High
2 AWG33.62 mm²115 A18.82 V (7.84%)221.2 V31.04 V (12.93%)22815.9 WDrop/Amp High
1 AWG42.41 mm²130 A14.92 V (6.22%)225.1 V24.61 V (10.25%)18087.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A11.83 V (4.93%)228.2 V19.51 V (8.13%)14340.5 WDrop/Amp High
2/0 AWG67.43 mm²175 A9.38 V (3.91%)230.6 V15.48 V (6.45%)11375.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A7.44 V (3.1%)232.6 V12.28 V (5.12%)9023.3 WDrop/Amp High
4/0 AWG107.2 mm²230 A5.9 V (2.46%)234.1 V9.74 V (4.06%)7155.5 WDrop/Amp High
250 kcmil126.7 mm²255 A4.99 V (2.08%)235.0 V8.24 V (3.43%)6054.2 WDrop/Amp High
300 kcmil152.0 mm²285 A4.16 V (1.73%)235.8 V6.87 V (2.86%)5046.5 WDrop/Amp High
350 kcmil177.3 mm²310 A3.57 V (1.49%)236.4 V5.89 V (2.45%)4326.4 WDrop/Amp High
400 kcmil202.7 mm²335 A3.12 V (1.3%)236.9 V5.15 V (2.15%)3784.3 WDrop/Amp High
500 kcmil253.4 mm²380 A2.5 V (1.04%)237.5 V4.12 V (1.72%)3027.1 WDrop/Amp High
600 kcmil304.0 mm²420 A2.08 V (0.87%)237.9 V3.43 V (1.43%)2523.3 WDrop/Amp High
750 kcmil380.0 mm²475 A1.66 V (0.69%)238.3 V2.75 V (1.14%)2018.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.25 V (0.52%)238.8 V2.06 V (0.86%)1513.9 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 80 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 80 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.62V (0.26%) and delivers 239.4V at the load.

What size aluminum wire is required for 700 amps at 80 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 2.06V (0.86%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.