⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 30 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 30 ft (9.1 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.1%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 0.77V (0.32%)
Voltage at Load End239.8 VLoss: 0.23 V (283.9 W)
Power & Breaker (125%)290.98 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 30 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A114.06 V (47.53%)125.9 V188.15 V (78.4%)138294.2 WDrop/Amp High
12 AWG3.31 mm²20 A71.68 V (29.87%)168.3 V118.23 V (49.26%)86903.9 WDrop/Amp High
10 AWG5.26 mm²30 A45.1 V (18.79%)194.9 V74.4 V (31.0%)54686.7 WDrop/Amp High
8 AWG8.37 mm²50 A28.35 V (11.81%)211.7 V46.76 V (19.48%)34367.0 WDrop/Amp High
6 AWG13.3 mm²65 A17.84 V (7.43%)222.2 V29.43 V (12.26%)21628.0 WDrop/Amp High
4 AWG21.15 mm²85 A11.22 V (4.67%)228.8 V18.5 V (7.71%)13600.6 WDrop/Amp High
3 AWG26.67 mm²100 A8.9 V (3.71%)231.1 V14.67 V (6.11%)10785.6 WDrop/Amp High
2 AWG33.62 mm²115 A7.06 V (2.94%)232.9 V11.64 V (4.85%)8556.0 WDrop/Amp High
1 AWG42.41 mm²130 A5.59 V (2.33%)234.4 V9.23 V (3.84%)6782.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A4.44 V (1.85%)235.6 V7.32 V (3.05%)5377.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A3.52 V (1.47%)236.5 V5.8 V (2.42%)4265.9 WDrop/Amp High
3/0 AWG85.01 mm²200 A2.79 V (1.16%)237.2 V4.6 V (1.92%)3383.7 WDrop/Amp High
4/0 AWG107.2 mm²230 A2.21 V (0.92%)237.8 V3.65 V (1.52%)2683.3 WDrop/Amp High
250 kcmil126.7 mm²255 A1.87 V (0.78%)238.1 V3.09 V (1.29%)2270.3 WDrop/Amp High
300 kcmil152.0 mm²285 A1.56 V (0.65%)238.4 V2.57 V (1.07%)1892.4 WDrop/Amp High
350 kcmil177.3 mm²310 A1.34 V (0.56%)238.7 V2.21 V (0.92%)1622.4 WDrop/Amp High
400 kcmil202.7 mm²335 A1.17 V (0.49%)238.8 V1.93 V (0.8%)1419.1 WDrop/Amp High
500 kcmil253.4 mm²380 A0.94 V (0.39%)239.1 V1.54 V (0.64%)1135.2 WDrop/Amp High
600 kcmil304.0 mm²420 A0.78 V (0.33%)239.2 V1.29 V (0.54%)946.2 WDrop/Amp High
750 kcmil380.0 mm²475 A0.62 V (0.26%)239.4 V1.03 V (0.43%)757.0 WDrop/Amp High
1000 kcmil506.7 mm²545 A0.47 V (0.2%)239.5 V0.77 V (0.32%)567.7 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 30 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 30 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.23V (0.1%) and delivers 239.8V at the load.

What size aluminum wire is required for 700 amps at 30 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 0.77V (0.32%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.