🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 120 Feet (240V Three-Phase (US Industrial Delta))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 120 ft (36.6 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 0.39%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 3.09V (1.29%)
Voltage at Load End239.1 VLoss: 0.94 V (1135.4 W)
Power & Breaker (125%)290.98 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 120 Feet (240V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A456.25 V (190.11%)0.0 V752.6 V (313.58%)553176.8 WDrop/Amp High
12 AWG3.31 mm²20 A286.71 V (119.46%)0.0 V472.94 V (197.06%)347615.7 WDrop/Amp High
10 AWG5.26 mm²30 A180.42 V (75.17%)59.6 V297.61 V (124.0%)218746.7 WDrop/Amp High
8 AWG8.37 mm²50 A113.38 V (47.24%)126.6 V187.03 V (77.93%)137468.1 WDrop/Amp High
6 AWG13.3 mm²65 A71.35 V (29.73%)168.6 V117.7 V (49.04%)86511.9 WDrop/Amp High
4 AWG21.15 mm²85 A44.87 V (18.7%)195.1 V74.01 V (30.84%)54402.3 WDrop/Amp High
3 AWG26.67 mm²100 A35.58 V (14.83%)204.4 V58.7 V (24.46%)43142.4 WDrop/Amp High
2 AWG33.62 mm²115 A28.23 V (11.76%)211.8 V46.56 V (19.4%)34223.9 WDrop/Amp High
1 AWG42.41 mm²130 A22.38 V (9.32%)217.6 V36.91 V (15.38%)27130.6 WDrop/Amp High
1/0 AWG53.49 mm²150 A17.74 V (7.39%)222.3 V29.27 V (12.19%)21510.7 WDrop/Amp High
2/0 AWG67.43 mm²175 A14.07 V (5.86%)225.9 V23.22 V (9.67%)17063.7 WDrop/Amp High
3/0 AWG85.01 mm²200 A11.16 V (4.65%)228.8 V18.41 V (7.67%)13535.0 WDrop/Amp High
4/0 AWG107.2 mm²230 A8.85 V (3.69%)231.1 V14.6 V (6.08%)10733.3 WDrop/Amp High
250 kcmil126.7 mm²255 A7.49 V (3.12%)232.5 V12.36 V (5.15%)9081.4 WDrop/Amp High
300 kcmil152.0 mm²285 A6.24 V (2.6%)233.8 V10.3 V (4.29%)7569.8 WDrop/Amp High
350 kcmil177.3 mm²310 A5.35 V (2.23%)234.6 V8.83 V (3.68%)6489.6 WDrop/Amp High
400 kcmil202.7 mm²335 A4.68 V (1.95%)235.3 V7.72 V (3.22%)5676.4 WDrop/Amp High
500 kcmil253.4 mm²380 A3.75 V (1.56%)236.3 V6.18 V (2.57%)4540.7 WDrop/Amp High
600 kcmil304.0 mm²420 A3.12 V (1.3%)236.9 V5.15 V (2.15%)3784.9 WDrop/Amp High
750 kcmil380.0 mm²475 A2.5 V (1.04%)237.5 V4.12 V (1.72%)3027.9 WDrop/Amp High
1000 kcmil506.7 mm²545 A1.87 V (0.78%)238.1 V3.09 V (1.29%)2270.8 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 120 feet (240V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 120 feet one-way at 240V (3-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 0.94V (0.39%) and delivers 239.1V at the load.

What size aluminum wire is required for 700 amps at 120 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 3.09V (1.29%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.