🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 1000 Feet (208V Three-Phase (US Commercial Wye))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 1000 ft (304.8 m) one-way run.

Copper Wire (≤3% Drop)3× 1000 kcmil (Parallel)506.7 mm² · Drop: 2.5%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 25.75V (12.38%)
Voltage at Load End202.8 VLoss: 5.2 V (6307.7 W)
Power & Breaker (125%)252.19 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 1000 Feet (208V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A3802.1 V (1827.93%)0.0 V6271.7 V (3015.24%)4609806.9 WDrop/Amp High
12 AWG3.31 mm²20 A2389.24 V (1148.67%)0.0 V3941.13 V (1894.77%)2896797.1 WDrop/Amp High
10 AWG5.26 mm²30 A1503.49 V (722.83%)0.0 V2480.06 V (1192.34%)1822889.4 WDrop/Amp High
8 AWG8.37 mm²50 A944.85 V (454.25%)0.0 V1558.56 V (749.31%)1145567.3 WDrop/Amp High
6 AWG13.3 mm²65 A594.61 V (285.87%)0.0 V980.84 V (471.56%)720932.2 WDrop/Amp High
4 AWG21.15 mm²85 A373.92 V (179.77%)0.0 V616.79 V (296.53%)453352.2 WDrop/Amp High
3 AWG26.67 mm²100 A296.53 V (142.56%)0.0 V489.13 V (235.16%)359520.0 WDrop/Amp High
2 AWG33.62 mm²115 A235.23 V (113.09%)0.0 V388.02 V (186.55%)285199.2 WDrop/Amp High
1 AWG42.41 mm²130 A186.47 V (89.65%)21.5 V307.6 V (147.88%)226088.1 WDrop/Amp High
1/0 AWG53.49 mm²150 A147.85 V (71.08%)60.2 V243.88 V (117.25%)179255.9 WDrop/Amp High
2/0 AWG67.43 mm²175 A117.28 V (56.39%)90.7 V193.46 V (93.01%)142197.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A93.03 V (44.73%)115.0 V153.45 V (73.78%)112791.4 WDrop/Amp High
4/0 AWG107.2 mm²230 A73.77 V (35.47%)134.2 V121.69 V (58.5%)89444.0 WDrop/Amp High
250 kcmil126.7 mm²255 A62.42 V (30.01%)145.6 V102.96 V (49.5%)75678.0 WDrop/Amp High
300 kcmil152.0 mm²285 A52.03 V (25.01%)156.0 V85.82 V (41.26%)63081.6 WDrop/Amp High
350 kcmil177.3 mm²310 A44.6 V (21.44%)163.4 V73.58 V (35.37%)54080.1 WDrop/Amp High
400 kcmil202.7 mm²335 A39.02 V (18.76%)169.0 V64.36 V (30.94%)47303.4 WDrop/Amp High
500 kcmil253.4 mm²380 A31.21 V (15.0%)176.8 V51.48 V (24.75%)37839.0 WDrop/Amp High
600 kcmil304.0 mm²420 A26.01 V (12.51%)182.0 V42.91 V (20.63%)31540.8 WDrop/Amp High
750 kcmil380.0 mm²475 A20.81 V (10.01%)187.2 V34.33 V (16.5%)25232.6 WDrop/Amp High
1000 kcmil506.7 mm²545 A15.61 V (7.5%)192.4 V25.75 V (12.38%)18923.2 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 1000 feet (208V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 1000 feet one-way at 208V (3-Phase), you need 3× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 5.2V (2.5%) and delivers 202.8V at the load.

What size aluminum wire is required for 700 amps at 1000 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 25.75V (12.38%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.