⚡ Cu ρ (75°C): 0.0214 Ω·mm²/m 🔌 NEC / IEC Standards: NFPA 70 & IEC 60364 🇺🇸 US Grid Avg: $0.175/kWh 🇩🇪 DE Grid Avg: €0.345/kWh 🇸🇪 SE Elpris: 1.54 SEK/kWh 🇳🇴 NO Strøm: 1.17 NOK/kWh 🔩 Copper Ref: $9,650/t (2026-10-24)
🇺🇸 NEC NFPA 70 · Table 310.16 (75°C) · Voltage Drop Analysis

700 Amp Wire Size at 150 Feet (120V Single-Phase (US Standard Branch))

Complete conductor sizing, Ohm's law voltage drop, $I^2R$ line power loss, and circuit breaker specification for a 700 A load over a 150 ft (45.7 m) one-way run.

Copper Wire (≤3% Drop)2× 1000 kcmil (Parallel)506.7 mm² · Drop: 1.12%
Aluminum Wire (≤3% Drop)1000 kcmilDrop: 4.46V (3.72%)
Voltage at Load End118.7 VLoss: 1.35 V (946.1 W)
Power & Breaker (125%)84.0 kW1000A Breaker Recommended

All AWG & kcmil Wire Gauges for 700 Amps at 150 Feet (120V)

Wire GaugeMetric AreaNEC 75°C Cu Ampacity Copper Voltage DropLoad VoltageAluminum DropLine Loss ($I^2R$)NEC Status
14 AWG2.08 mm²15 A658.54 V (548.79%)0.0 V1086.29 V (905.24%)460980.7 WDrop/Amp High
12 AWG3.31 mm²20 A413.83 V (344.86%)0.0 V682.62 V (568.85%)289679.7 WDrop/Amp High
10 AWG5.26 mm²30 A260.41 V (217.01%)0.0 V429.56 V (357.97%)182288.9 WDrop/Amp High
8 AWG8.37 mm²50 A163.65 V (136.38%)0.0 V269.95 V (224.96%)114556.7 WDrop/Amp High
6 AWG13.3 mm²65 A102.99 V (85.83%)17.0 V169.89 V (141.57%)72093.2 WDrop/Amp High
4 AWG21.15 mm²85 A64.76 V (53.97%)55.2 V106.83 V (89.03%)45335.2 WDrop/Amp High
3 AWG26.67 mm²100 A51.36 V (42.8%)68.6 V84.72 V (70.6%)35952.0 WDrop/Amp High
2 AWG33.62 mm²115 A40.74 V (33.95%)79.3 V67.21 V (56.01%)28519.9 WDrop/Amp High
1 AWG42.41 mm²130 A32.3 V (26.92%)87.7 V53.28 V (44.4%)22608.8 WDrop/Amp High
1/0 AWG53.49 mm²150 A25.61 V (21.34%)94.4 V42.24 V (35.2%)17925.6 WDrop/Amp High
2/0 AWG67.43 mm²175 A20.31 V (16.93%)99.7 V33.51 V (27.92%)14219.8 WDrop/Amp High
3/0 AWG85.01 mm²200 A16.11 V (13.43%)103.9 V26.58 V (22.15%)11279.1 WDrop/Amp High
4/0 AWG107.2 mm²230 A12.78 V (10.65%)107.2 V21.08 V (17.56%)8944.4 WDrop/Amp High
250 kcmil126.7 mm²255 A10.81 V (9.01%)109.2 V17.83 V (14.86%)7567.8 WDrop/Amp High
300 kcmil152.0 mm²285 A9.01 V (7.51%)111.0 V14.87 V (12.39%)6308.2 WDrop/Amp High
350 kcmil177.3 mm²310 A7.73 V (6.44%)112.3 V12.74 V (10.62%)5408.0 WDrop/Amp High
400 kcmil202.7 mm²335 A6.76 V (5.63%)113.2 V11.15 V (9.29%)4730.3 WDrop/Amp High
500 kcmil253.4 mm²380 A5.41 V (4.5%)114.6 V8.92 V (7.43%)3783.9 WDrop/Amp High
600 kcmil304.0 mm²420 A4.51 V (3.75%)115.5 V7.43 V (6.19%)3154.1 WDrop/Amp High
750 kcmil380.0 mm²475 A3.6 V (3.0%)116.4 V5.95 V (4.96%)2523.3 WDrop/Amp High
1000 kcmil506.7 mm²545 A2.7 V (2.25%)117.3 V4.46 V (3.72%)1892.3 WDrop/Amp High

Frequently Asked Engineering Questions

What size copper wire do I need for 700 amps at 150 feet (120V)?

To stay within the NEC recommended 3% maximum voltage drop for a 700A load over 150 feet one-way at 120V (1-Phase), you need 2× 1000 kcmil (Parallel) copper wire. This produces a voltage drop of 1.35V (1.12%) and delivers 118.7V at the load.

What size aluminum wire is required for 700 amps at 150 feet?

Using aluminum conductors (75°C rating), you should use 1000 kcmil to maintain voltage drop at 4.46V (3.72%).

What breaker size is needed for a 700A continuous load?

Under NEC 210.20(A), continuous loads require a circuit breaker rated at 125% of the continuous current (700A × 1.25 = 875.0A), which corresponds to a standard 1000A circuit breaker.